SFC Task Control Instruction Specifications
Appendix B
126
B-2
SFC PAUSE WITH RESET (SFCPR)/SFC PAUSE NO WITH
RESET(SFCPRN)
SFCPR Instruction
Outline
Pauses execution of an SFC task. The status of all
outputs is reset. When execution of a paused task
is restarted, execution will start from the step that
was active when the task was paused.
Symbol
SFCPR
N
N: SFC task number
Operands
Cyclic Task
For CJ2
N: &0 to &128 (Correspond to cyclic tasks 0 to
128.)
For other models
N: &0 to &31 (Correspond to cyclic tasks 0 to 31.)
Description
Execution of the SFC task specified by N is
paused.
All outputs from the paused task are reset.
When the paused task is restarted with the
SFCON instruction, it is executed from the status
that existed before it was paused.
Variations
Executed Each Cycle for ON
Condition
SFCPR
Variations
Executed Once for Upward
Differentiation
None
Immediate Refreshing Specification
None
SFCPRN Instruction
Outline
Pauses execution of an SFC task. The status of all
outputs is held. When execution of a paused task
is restarted, execution will start from the step that
was active when the task was paused.
Symbol
SFCPRN
N
N: SFC task number
Operands
Cyclic Task
For CJ2
N: &0 to &128 (Correspond to cyclic tasks 0 to
128.)
For other models
N: &0 to &31 (Correspond to cyclic tasks 0 to 31.)
Description
Execution of the SFC task specified by N is
paused.
All outputs from the paused task are held.
When the paused task is restarted with the
SFCON instruction, it is executed from the status
that existed before it was paused.
Variations
Executed Each Cycle for ON
Condition
SFCPRN
Variations
Executed Once for Upward
Differentiation
None
Immediate Refreshing Specification
None
Applicable Program Areas
SFCPR/SFCPRN
Area
Function
block
definitions
Block
program
areas
Step
program
areas
Subroutines Interrupt
task
programs
Usage
OK OK OK OK OK
Operand Data
SFCPR/SFCPRN
Task name
Operand
0 to 128 (for CJ2)
&0 to &128
Cyclic tasks
0 to 31 (for other models)
&0 to &31
Extra task 0 (interrupt task 0)
&8000
Extra task 1 (interrupt task 1)
&8001
…. …
Extra task 255 (interrupt task 255)
&8255
Содержание SYSMAC CX-Programmer 8.1
Страница 1: ...Operation Manual SFC Programming SYSMAC WS02 CXPC1 V8 CX Programmer Ver 8 1 Cat No W469 E1 04...
Страница 2: ...ii CX Programmer Ver 8 1 WS02 CXPC1 V8 Operation Manual SFC Programming Revised February 2009...
Страница 16: ......
Страница 56: ...Precautions When Creating SFC Programs Section 1 5 40...
Страница 117: ...Monitoring Section 4 5 101 For details refer to 3 2 3 Adding an Action to a Step or to the Initial Step...
Страница 118: ...Monitoring Section 4 5 102...
Страница 150: ...Index 134...
Страница 152: ...Revision History 136...
Страница 153: ......
Страница 154: ......