25
Unit Components
Section 2-1
2-1-2
Indicators
The PROFIBUS-DP Master Units are each fitted with seven LEDs to indicate
the operational mode and status of the Unit and the PROFIBUS network
Indicator specifications
Note Unless otherwise specified, the frequency of a flashing LED is 1 Hz (50% duty
cycle).
CJ1W-PRM21
CS1W-PRM21
PRM21
CS
CS
RUN
RUN
ERC
ERC
BST
BST
BF
BF
ERH
ERH
PRM
PRM
COMM
COMM
ERC
RUN
BF
PRM21
COMM
BST
ERH
PRM
Indicator
Color
Status
Meaning
RUN
Green
Not lit
• Startup test failed, Unit not operational.
• Operation stopped, due to a fatal error.
Lit
Initialization successful, Unit is in normal operation.
ERC
(PROFIBUS-DP Master
Unit Error)
Red
Not lit
Unit is in normal operation.
Lit
One of the following errors occurred:
• Startup error.
• Non-volatile memory error (checksum failed, write-verify failed).
• Invalid PROFIBUS parameter configuration setting.
• Fatal error in program execution.
ERH
(PLC Error)
Red
Not lit
PLC CPU in normal operation.
Lit
One of the following errors occurred:
• PLC CPU Bus error.
• Cyclic Refresh Monitor Time-out.
PRM
(Parameter database)
Green
Not lit
PROFIBUS Parameter configuration is not available or incorrect.
Flashing
PROFIBUS Parameter configuration is being transferred to the Unit and
is not yet available.
Lit
PROFIBUS Parameter configuration is correct, and operational.
BST
(Bus status)
Green
Not lit
The PROFIBUS-DP Master Unit is in OFFLINE or STOP mode.
Flashing
The PROFIBUS-DP Master Unit is in CLEAR mode.
Lit
The PROFIBUS-DP Master Unit is in OPERATE mode.
COMM
(I/O Data communication)
Green
Not lit
No PROFIBUS data exchange with any of the allocated slaves.
Flashing
Fatal error occurred (ERC LED is ON). Unit initialization failed.
Lit
PROFIBUS data exchange ongoing with at least one allocated slave.
BF
(Bus Fail)
Red
Not lit
No PROFIBUS communication errors occurred.
Flashing
At least one allocated slave is not in data exchange with the Unit.
Lit
An error occurred in the PROFIBUS interface of the Unit
(see section
Содержание SYSMAC CJ1W-PRM21
Страница 2: ...iv...
Страница 36: ...22 Basic Operating Procedure Section 1 5...
Страница 52: ...38 Defining PROFIBUS DP in the Software Section 2 5...
Страница 112: ...98 Allocated CIO Area Words Section 4 2...
Страница 122: ...108 Command Response Reference Section 5 2...
Страница 160: ...146 Replacing the Unit Section 7 8...
Страница 174: ...160 Appendix...
Страница 180: ...166 I O Data Conversions Appendix D...
Страница 186: ...172 Configurator Error and Warning Messages Appendix E...
Страница 187: ...173 Index...
Страница 188: ...174 Index...
Страница 190: ...176 Revision History...