3 Assigning Device Variables for CJ-series Units
3-14
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
*_DNSSvrErr
BOOL
R
DNS Server Error
TRUE:
The DNS client failed to connect to the DNS
server (timeout).
FALSE: DNS is not set up. Or, DNS server informa-
tion is set and the connection was success-
ful.
*_RTblErr
BOOL
R
Routing Table Error
TRUE:
The routing table information is not correct.
FALSE: The routing table information is correct.
*_ETNAdvSetErr
BOOL
R
Ethernet Advanced
Setting Error
TRUE:
One of the following Ethernet settings is not
correct.
•
FINS settings
FALSE: The settings are normal.
*_BootpSvrErr
BOOL
R
BOOTP Server Error
TRUE:
There was a failure to connect to the
BOOTP server (timeout).
FALSE: The BOOTP is not set up, or the BOOTP
server is set up and an IP address was nor-
mally obtained from the BOOTP server.
*_SNTPSvrErr
BOOL
R
SNTP Server Error
TRUE:
The SNTP client failed to connect to the
server (timeout).
FALSE: SNTP is not set up or SNTP is set up and
the connection was successful.
*_AdrMismatchErr
BOOL
R
Address Mismatch
TRUE:
The target IP address conversion method is
set to Automatic generation, but the local IP
address' host ID does not match the FINS
node address.
FALSE: Other than the above setting status.
*_MemErr
BOOL
R
Non-volatile Memory
Error
TRUE:
There is an error in the non-volatile memory
in EtherNet/IP Unit.
FALSE: The non-volatile memory in EtherNet/IP Unit
is normal.
Device variable name for CJ-
series Unit
Data
type
R/W
Meaning
Description
Содержание SYSMAC CJ1W-EIP21
Страница 8: ...Manual Structure 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 10: ...Sections in this Manual 8 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 20: ...Read and Understand this Manual 18 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 42: ...Revision History 40 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 68: ...1 Introduction 1 26 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 80: ...2 Installing Ethernet Networks 2 12 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 130: ...6 Testing Communications 6 4 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 206: ...7 Tag Data Link Functions 7 76 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 246: ...8 Message Communications 8 40 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 266: ...9 FTP Server 9 20 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 374: ...13 Troubleshooting 13 56 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 431: ...Index 1 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 I Index...
Страница 436: ...Index 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 Index...
Страница 437: ......