13 Troubleshooting
13-16
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
* The 7-segment display alternates between the node address and error code.
Indicator
Error
Cause
Unit operation
Error log
(hex)
Countermeasure
MS
NS
7-seg-
ment*
Errors Related to Memory Access
Flash-
ing red
---
EA
IP Advanced Set-
tings Error
There is an error in the
parameter settings stored
in the Unit's non-volatile
memory. (An error can
occur when power is
interrupted while data is
being written to non-vola-
tile memory.)
The Unit Error Occurred
Flag (n+10, bit 00) and
Invalid Communications
Parameter Flag (n+12, bit
04) will go ON.
03D1
Identify the error log
data, correct the set-
tings, and then down-
load the Unit Setup
from the tab pages of
the Edit Parameters
Dialog Box of the
Sysmac Studio.
Flash-
ing red
---
F2
Ethernet Basic
Settings Error
---
03D0
Download the set-
tings from the TCP/IP
or Ethernet Tab
Pages of the Edit
Parameters Dialog
Box of the Sysmac
Studio or download
the TCP/IP settings
from the Network
Configurator.
---
---
E1
Ethernet Link Not
Detected
The link with the
Ethernet switch could
not be detected.
Note
This error will
not occur when
data links are
not set.
•
The Unit will be offline
and unable to commu-
nicate. Errors will be
returned to all commu-
nications requests.
•
Data exchanges
(refreshing) will con-
tinue with the CPU Unit.
*_UnitErr (Unit Error
Occurred), *_NetErr (Net-
work Error Occurred),
and *_LkOffErr (Link OFF
Error) will change to
TRUE. *_LkSta (Link Sta-
tus) will change to
FALSE.
03D3
Check the following
items:
•
Is the cable con-
nected?
•
Is the cable dam-
aged or loose?
•
Is there excessive
noise?
Содержание SYSMAC CJ1W-EIP21
Страница 8: ...Manual Structure 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 10: ...Sections in this Manual 8 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 20: ...Read and Understand this Manual 18 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 42: ...Revision History 40 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 68: ...1 Introduction 1 26 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 80: ...2 Installing Ethernet Networks 2 12 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 130: ...6 Testing Communications 6 4 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 206: ...7 Tag Data Link Functions 7 76 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 246: ...8 Message Communications 8 40 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 266: ...9 FTP Server 9 20 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 374: ...13 Troubleshooting 13 56 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 431: ...Index 1 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 I Index...
Страница 436: ...Index 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 Index...
Страница 437: ......