13-23
13 Troubleshooting
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
13
-3 Co
nn
ectio
n Status C
ode
s and
Er
ro
r Pr
oc
essing
13
01
011B
Error code returned from tar-
get:
The RPI was set to a value
that is below the specifica-
tions.
This error does
not occur.
Depends on
the target’s
specifications.
(Contact the
target device’s
manufacturer.)
Set the origina-
tor’s RPI setting
to 0.5 ms or
greater.
01
0203
Error code returned from tar-
get:
The connection timed out.
Tag data link communications from the target timed
out. Check the power supply and cable wiring of the
devices in the communications path, including the
target and switches. If performance has dropped
due to heavy load, change the performance set-
tings. For example, increase the timeout time or RPI
setting.
01
0204
Error code returned from tar-
get:
The connection-opening pro-
cess timed out.
There was no response from the target. Check the
power supply and cable wiring of the devices in the
communications path, including the target and
switches.
01
0205
Error code returned from tar-
get:
There was a parameter error
in the frame used to open the
connection.
This error does
not occur.
Depends on
the target’s
specifications.
(Contact the
target device’s
manufacturer.)
Depends on
the originator’s
specifications.
(Contact the
originator
device’s manu-
facturer.)
01
0302
Error occurred at originator or
error code returned from tar-
get:
The tag data link’s allowable
bandwidth (pps) was
exceeded.
Check the origi-
nator and tar-
get connection
settings (num-
ber of connec-
tions and RPI).
Check the tar-
get’s connec-
tion settings
(number of con-
nections and
RPI).
Check the origi-
nator and tar-
get connection
settings (num-
ber of connec-
tions and RPI).
01
0311
Error code returned from tar-
get:
There was a parameter error
in the frame used to open the
connection.
This error does
not occur.
Depends on
the target’s
specifications.
(Contact the
target device’s
manufacturer.)
Depends on
the originator’s
specifications.
(Contact the
originator
device’s manu-
facturer.)
01
0312
Error code returned from tar-
get:
There was a parameter error
in the frame used to open the
connection.
This error does
not occur.
Depends on
the target’s
specifications.
(Contact the
target device’s
manufacturer.)
Depends on
the originator’s
specifications.
(Contact the
originator
device’s manu-
facturer.)
01
0315
Error code returned from tar-
get:
There was a parameter error
in the frame used to open the
connection.
This error does
not occur.
Depends on
the target’s
specifications.
(Contact the
target device’s
manufacturer.)
Depends on
the originator’s
specifications.
(Contact the
originator
device’s manu-
facturer.)
01
0316
Error code returned from tar-
get:
There was a parameter error
in the frame used to close the
connection.
This error does
not occur.
Depends on
the target’s
specifications.
(Contact the
target device’s
manufacturer.)
Depends on
the originator’s
specifications.
(Contact the
originator
device’s manu-
facturer.)
Connection status
Source of error
Handling
General
Status
(hex)
Additional
Status
(hex)
Configuration
1
Configuration
2
Configuration
2
Содержание SYSMAC CJ1W-EIP21
Страница 8: ...Manual Structure 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 10: ...Sections in this Manual 8 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 20: ...Read and Understand this Manual 18 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 42: ...Revision History 40 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 68: ...1 Introduction 1 26 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 80: ...2 Installing Ethernet Networks 2 12 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 130: ...6 Testing Communications 6 4 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 206: ...7 Tag Data Link Functions 7 76 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 246: ...8 Message Communications 8 40 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 266: ...9 FTP Server 9 20 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 374: ...13 Troubleshooting 13 56 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 431: ...Index 1 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 I Index...
Страница 436: ...Index 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 Index...
Страница 437: ......