8-37
8 Message Communications
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
8-3 C
IP Ob
jects Sen
t to the Eth
erNet/IP U
n
it
8
8
-3
-4 Ether
net Link Object (Class ID
: F6 H
e
x)
(1) Interface Flag Details
05 hex
Media Counters
Media counters for the Ether-
Net/IP Unit.
Read
Struct
---
Alignment Errors
Number of frames received that
were not octets in length.
UDINT
Reads the current value.
FCS Errors
Number of frames received that
did not pass the FCS check.
UDINT
Reads the current value.
Single Collisions
Number of frames sent success-
fully with only one collision.
UDINT
Reads the current value.
Multiple Collisions
Number of frames sent success-
fully with two or more collisions.
UDINT
Reads the current value.
SQE Test Errors
Number of times a SQE test error
message was generated.
UDINT
Reads the current value.
Deferred Transmissions
The number of frames for which
the first attempt to send was
delayed because the media was
busy.
UDINT
Reads the current value.
Late Collisions
The number of collisions detected
in packets that were sent after
512 bit times.
UDINT
Reads the current value.
Excessive Collisions
The number of frames that failed
to be sent because of excessive
collisions.
UDINT
Reads the current value.
MAC Transmit Errors
The number of frames that failed
to be sent due to an internal MAC
sublayer transmission error.
UDINT
Reads the current value.
Carrier Sense Errors
The number of times the carrier
sense condition was lost or the
number of times an assertion did
not occur when an attempt was
made to send the frame.
UDINT
Reads the current value.
Frame Too Long
The number of frames received
that exceeded the maximum
allowed frame size.
UDINT
Reads the current value.
MAC Receive Errors
The number of frames that could
not be received through the inter-
face due to an internal MAC sub-
layer reception error.
UDINT
Reads the current value.
06 hex
Interface Control
Counter for the EtherNet/IP Unit.
Write
Struct
---
Software Switches
Auto Nego for Ethernet communi-
cations that specifies full duplex.
WORD
Refer to (2) Software Switch
Details, below.
Forced Interface Speed
Gives the set value of the Ether-
net baud rate.
UINT
Reads the set value.
Bit
Name
Description
0
LinkStatus
FALSE: The link is down.
TRUE: The link is up.
1
Half/FullDuplex
FALSE: Half duplex
TRUE: Full duplex
2 to 4
Negotiation Status
00 hex: Auto-negotiation is in progress.
01 hex: Auto-negotiation and speed detection failed.
02 hex: Auto-negotiation failed, but speed detection succeeded.
03 hex: Speed and duplex mode negotiation succeeded.
04 hex: Auto-negotiation was not attempted.
5
Manual Setting Requires Speed
Always FALSE: Changes can be applied automatically.
6
Local Hardware Fault
Always FALSE
7 to 31
Reserved
Always FALSE
Attribute ID
Parameter name
Description
Attribute
Read/write data
Data
type
Value
Содержание SYSMAC CJ1W-EIP21
Страница 8: ...Manual Structure 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 10: ...Sections in this Manual 8 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 20: ...Read and Understand this Manual 18 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 42: ...Revision History 40 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 68: ...1 Introduction 1 26 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 80: ...2 Installing Ethernet Networks 2 12 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 130: ...6 Testing Communications 6 4 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 206: ...7 Tag Data Link Functions 7 76 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 246: ...8 Message Communications 8 40 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 266: ...9 FTP Server 9 20 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 374: ...13 Troubleshooting 13 56 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 431: ...Index 1 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 I Index...
Страница 436: ...Index 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 Index...
Страница 437: ......