1-8-3 Terminals
Main Circuit
Terminal
Description
L1 (R)
Main circuit power input
“L1” “L2”
d f
i
l
h
i
t
ifi
ti
L2 (S)
“L1”, “L2” are used for single-phase input specifications.
L3 (T)
T1 (U)
Inverter output
T2 (V)
T3 (W)
B1
Braking unit or braking unit resistor connector
B2
FLT-A
Contact capacity for fault signal output
“Closed” between A and C at fault
FLT-B
“Closed” between A and C at fault
“Open” between B and C at fault
250 VAC 1 A or less
FLT-C
250 VAC 1 A or less
30 VDC 1 A or less
G (E)
Grounding (ground resistance should be 100
or less)
L1 (R)
L2 (S)
L3 (T)
T1 (U)
T2 (V)
T3 (W)
FLT-A
FLT-B
FLT-C
B1
B2
E
L1 (R)
L2 (S)
T1 (U)
T2 (V)
T3 (W)
FLT-A
FLT-B
FLT-C
B1
B2
E
3-phase
Single-phase
Main Circuit Terminals
Input
Input
Out
put
Out
put
Faul
t
Faul
t
O
B
re
sisto
r
O
B
re
sisto
r
FG
FG
Section 1-8
Содержание SYSDRIVE 3G3SV