(-
Each time one of OC, OV, OH, or GF fault occurs, one is added to
the number of auto reset/restart operation, and auto reset/restart
operation is performed according to the following procedure. How-
ever, auto reset/restart operation is not performed in the following
cases:
Note
GF is for single-phase input models only.
The number of auto reset/restart operation is cleared to zero when:
1, 2, 3...
1. No fault occurs for 10 minutes or more.
2. A fault reset signal is input from external terminals or digital op-
erator.
2-10-23 Setting Prohibit Frequency Range (No. 50 to No. 53)
Set the range of setting prohibit frequency in the units of 0.1 Hz.
The range of the setting prohibit frequency is determined as fol-
lows, depending on combinations with No. 50 to No. 52.
No. 50 to No. 52 -- No. 53
≤
the range of the setting prohibit frequen-
cy
≤
No. 50 to No. 52 + No. 53
Setting prohibit
frequency
Setting prohibit
frequency
Setting prohibit
frequency
Setting prohibit
frequency Range
Internal frequency
REF.
No. 53
No. 51
No. 50
No.52
Setting frequency ref.
See note 2
Note
1. Constant-speed operation is prohibited in the setting prohibit
frequency range. Output frequency does not jump during ac-
celeration or deceleration, which is performed smoothly.,
2. Set as follows; No. 50
≥
No. 51
≥
No. 52
2-10-24 Speed Search Function
Item name
Constant to be set
Factory preset
Multifunction contact input function
No. 32, 33
---
Speed search deactive current level
No. 54
150%
Minimum baseblock time
No. 55
0.5 s
V/f during speed search
No. 56
100%
When search command is “closed” during baseblock, speed
search is started after inverter output is shut off for the minimum
baseblock time.
Search Command (Set
Value = 6, 7) (No. 32 or
No. 33)
Section 2-10
Содержание SYSDRIVE 3G3SV
Страница 1: ...6 6 5 9 69 19 57 5 69 BB 69 BB 2SHUDWLRQ 0DQXDO...
Страница 3: ...0 1 2 3...
Страница 5: ...2 4 4 3 4 5 5 6 7 8 8...