5-10 Analog Monitor Output
The 3G3JV incorporates analog monitor output terminals AM and AC.
These terminals have analog monitor values of output frequency or current.
H
Setting the Analog Monitor Output (n44 and n45)
•
The output frequency or current as a monitored item is set in n44.
•
The analog output characteristics are set as an analog monitor output gain in n45.
n44
Analog Monitor Output
Changes during
operation
No
Setting
range
0, 1
Unit of
setting
1
Default setting
0
Set Values
Value
Description
0
Output frequency (Reference: 10 V at max. frequency)
1
Output current (Reference: 10 V with rated output current)
n45
Analog Monitor Output Gain
Changes during
operation
Yes
Set range
0.00 to 2.00
Unit of
setting
0.01
Default setting
1.00
Note 1.
Set the multiplication ratio based on the set value in n44.
For example, if an output of 5 V is desired at maximum frequency (with n44 set to 0), set n45 to
0.50.
Note 2.
The maximum output voltage of the analog monitor output terminals are 10 V.
Basic Operation
Chapter 5
Содержание SYSDRIVE 3G3JV-A4002
Страница 1: ...USER S MANUAL SYSDRIVE 3G3JV Compact Simplified Inverters Cat No I528 E1 04...
Страница 3: ...USER S MANUAL Compact Simplified Inverter SYSDRIVE 3G3JVSERIES...
Страница 16: ......
Страница 20: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1...
Страница 26: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Страница 57: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Outline of Operation 3...
Страница 65: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Страница 190: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Specifications of Accessories 9 3 Option Specifications 9...
Страница 216: ...Chapter 10 List of Parameters 10...
Страница 229: ...Chapter 11 Using the Inverter for a Motor 11...