Procedure for Test Run
1. Installation and Mounting
Install the Inverter according to the installation conditions. Refer to page 2-2. Ensure that the instal-
lation conditions are met.
2. Wiring and Connection
Connect to the power supply and peripheral devices. Refer to page 2-7. Select peripheral devices
which meet the specifications and wire correctly.
3. Power Connection
Carry out the following pre-connection checks before turning on the power supply.
S
Always ensure that a power supply to the correct voltage is used and that the power input terminals
(R/L1, S/L2, and T/L3) are wired correctly.
3G3JV-A2
j
: 3-phase 200 to 230 V AC
3G3JV-AB
j
: Single-phase 200 to 240 V AC (Wire R/L1 and S/L2)
3G3JV-A4
j
: 3-phase 380 to 460 V AC
S
Make sure that the motor output terminals (U/T1, V/T2, and W/T3) are connected to the motor
correctly.
S
Ensure that the control circuit terminals and the control device are wired correctly. Make sure that
all control terminals are turned off.
S
Set the motor to no-load status (i.e., not connected to the mechanical system).
S
Having conducted the above checks, connect the power supply.
4. Check the Display Status
Check to be sure that there are no faults in the Inverter.
S
If the display at the time the power is connected is normal, it will read as follows:
RUN indicator: Flashes
ALARM indicator: Off
Setting/Monitor indicators: FREF, FOUT, or IOUT is lit.
Data display: Displays the corresponding data of the indicator that is lit.
S
When a fault has occurred, the details of the fault will be displayed. In that case, refer to
Chapter 8
Maintenance Operations
and take necessary remedies.
5. Initializing Parameters
Initialize the parameters.
S
Set n01 to 8 for initialization in 2-wire sequence.
6. Setting Parameters
Set the parameters required for a test run.
S
Set the rated motor current in order to prevent the motor from burning due to overloading.
7. No-load Operation
Start the no-load motor using the Digital Operator.
S
Set the frequency reference using the Digital Operator and start the motor using key sequences.
Test Run
Chapter 4
Содержание SYSDRIVE 3G3JV-A4002
Страница 1: ...USER S MANUAL SYSDRIVE 3G3JV Compact Simplified Inverters Cat No I528 E1 04...
Страница 3: ...USER S MANUAL Compact Simplified Inverter SYSDRIVE 3G3JVSERIES...
Страница 16: ......
Страница 20: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1...
Страница 26: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Страница 57: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Outline of Operation 3...
Страница 65: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Страница 190: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Specifications of Accessories 9 3 Option Specifications 9...
Страница 216: ...Chapter 10 List of Parameters 10...
Страница 229: ...Chapter 11 Using the Inverter for a Motor 11...