7-24
Note
There is an OR relationship between input from the control terminals and input through commu-
nications, except for the RUN command and forward/reverse rotation command.
D
Inverter Output (Register 0009 Hex)
Bit No.
Function
0
Multi-function contact output (1: ON)
1 to 15
Not used.
Note
The settings will be enabled if multi-function output n40 is set to 18 for communications output.
Then the output terminals (MA to MC) will be turned ON and OFF through communications.
H
Broadcast Message with Slave Address: 00 (00 Hex)
Write
Register No.
(Hex)
Function
Description
0000
Not used.
---
0001
RUN command
Refer to the table below.
0002
Frequency reference
Set the frequency reference based on the maximum
frequency as 30,000.
0003 to 000F
Not used.
---
Note 1.
Data can be written to registers 0001 and 0002 only. Assumed previous values are held for
unused registers.
Note 2.
No data can be written to multi-function input.
Note 3.
The unit of setting of the broadcast message is different from that in the DSR message to com-
municate with a single Slave.
D
RUN Command (Register 0001 Hex)
Bit No.
Function
0
RUN command (1: RUN)
1
Forward/Reverse (1: Reverse)
2 to 3
Not used.
4
External fault (1: External fault EF0)
5
Fault reset (1: Fault reset)
4 to 15
Not used.
7-7-2 Monitor Functions
Register No.
(Hex)
Function
Description
0020
Status signal
Refer to the following corresponding table.
0021
Fault status
Refer to the following corresponding table.
0022
Data link status
Refer to the following corresponding table.
0023
Frequency reference
According to the set value in n69.
0024
Output frequency
According to the set value in n69.
0025 to 0026
Not used.
---
Communications
Chapter 7
Содержание SYSDRIVE 3G3JV-A4002
Страница 1: ...USER S MANUAL SYSDRIVE 3G3JV Compact Simplified Inverters Cat No I528 E1 04...
Страница 3: ...USER S MANUAL Compact Simplified Inverter SYSDRIVE 3G3JVSERIES...
Страница 16: ......
Страница 20: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1...
Страница 26: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Страница 57: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Outline of Operation 3...
Страница 65: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Страница 190: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Specifications of Accessories 9 3 Option Specifications 9...
Страница 216: ...Chapter 10 List of Parameters 10...
Страница 229: ...Chapter 11 Using the Inverter for a Motor 11...