![Omron SYSDRIVE 3G3JV-A4002 Скачать руководство пользователя страница 205](http://html1.mh-extra.com/html/omron/sysdrive-3g3jv-a4002/sysdrive-3g3jv-a4002_user-manual_742832205.webp)
9-16
9-2-11 AC Reactor
H
3G3IV-PUZBAB
j
(Yaskawa Electric)
The AC Reactor suppresses harmonic current generated from the Inverter and improves the power fac-
tor of the Inverter. Connect the AC Reactor to the Inverter if the capacity of the power supply is much
larger than that of the Inverter. Select the AC Reactor model from the following table according to the
motor capacity.
H
Connection Example
MCCB AC Reactor
Motor
H
Applicable Range
Power supply
capacity (kVA)
AC Reactor required
for smooth operation
under present power
supply conditions
AC Reactor
not required
Inverter capacity (kVA)
H
Applicable Models and Dimensions
D
200-V Class
Max. applicable
motor capacity (kW)
Model
3G3IV-
PUZBAB
j
Current (A)
Inductance
(mH)
Loss (W)
Weight (kg)
0.1 to 0.2
2A7.0MH
2
7.0
8
2.5
0.4
2.5A4.2MH
2.5
4.2
15
2.5
0.75
5A2.1MH
5
2.1
15
2.5
1.5
10A1.1MH
10
1.1
25
3
2.2
15A0.71MH
15
0.71
30
3
3.7
20A0.53MH
20
0.53
35
3
Specifications
Chapter 9
Содержание SYSDRIVE 3G3JV-A4002
Страница 1: ...USER S MANUAL SYSDRIVE 3G3JV Compact Simplified Inverters Cat No I528 E1 04...
Страница 3: ...USER S MANUAL Compact Simplified Inverter SYSDRIVE 3G3JVSERIES...
Страница 16: ......
Страница 20: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1...
Страница 26: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Страница 57: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Outline of Operation 3...
Страница 65: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Страница 190: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Specifications of Accessories 9 3 Option Specifications 9...
Страница 216: ...Chapter 10 List of Parameters 10...
Страница 229: ...Chapter 11 Using the Inverter for a Motor 11...