48
9. Changing the setting of the functions
●
Setting steps
1. Unplug the UPS and let it to a standstill. Press the Start switch for at least 0.5 second while pressing and
holding Stop switch.
2. The AC Input Lamp blinks and the Bypass Mode Lamp or
the Battery Mode Lamp goes on.
3. Under the condition, press and hold the Start Switch again
for at least 0.5 second. Either of the Bypass Mode Lamp or
the Battery Mode Lamp turns on, and let the setting change.
•
The Bypass Mode Lamp lights up:
It lets the UPS accept the signal both during line mode
and battery mode.
You can bring the UPS into a standstill by the voltage sig-
nal, which continues at least 10 seconds.
•
The Battery Mode Lamp lights up:
It lets the UPS accept the battery mode only.
You can bring the UPS into a standstill by voltage signal,
which continues at least 0.01 second (10 ms).
* Factory-setting: Accept BS signal only during Battery
mode.
4. When the desired setting is displayed, press and hold the Stop switch for at least 2 seconds, and then the
setting is completed.
9-2 Functions that can be set/change from the
UPS monitoring software
1. Beeper ON/OFF setting
ON : The beeper sounds when an alarm is necessary.
OFF : Let the beeper disable.
* Factory-setting: ON
2. Auto battery test ON/OFF
ON : The battery test is automatically executed every 4 weeks.
If the test decides that the battery needs replacing, the UPS generates a replacement alarm.
OFF : The battery test, which is executed automatically at intervals of 4 weeks, comes to a standstill.
Set the test OFF in the cases where you want to let the automatic battery test and battery mode
come a standstill.
* Factory-setting: ON
3. Auto restart ON/OFF
ON : The UPS startup automatically and starts to feed power at the time when the commercial power is
restored. It always takes place after the UPS is shut down through UPS monitoring software or the
contact signal in the event of power failures.
OFF : The UPS will not startup automatically at the time when the commercial power is restored following
the shutdown of the UPS through UPS monitoring software or the contact signal. You only can start
up the UPS manually by pressing the Start switch.
* Factory-setting: ON