13
2. Installation and connection
Notes
For safety installation, placing a rail or steel plate is recommended to support the
weight of the USP.
●
The weight of the UPS
BU100XR2: 19kg
BU200XR2: 12kg (main unit)
MB100XR2: 26kg (add-on battery unit)
MB200XR2: 26kg (battery unit)
Place the UPS on the lowest part of lack.
●
When connecting the battery unit and/or adding another battery unit, be sure to place the battery unit on the
lower part of main unit.
Do not give a short between the output lines of the UPS, as well as a ground fault
between the output lines and the ground.
●
The UPS may fail.
Do not put the AC Input Plug of the UPS in the Power Supply Output Receptacle of
the UPS.
●
The UPS may fail.
Do not connect a page printer to the UPS.
●
In a case a page printer is connected to the UPS, the amount of output current often exceeds the current
output capacity of the UPS in the commercial power operating mode, and that may lead to the UPS to put
out a feed power as it is (bypass mode).
●
The peak current of the page printer is large so that it may be detected as an overcurrent.
Cautions
(Prohibition (don'ts))
Do not obstruct the air inlets and outlets on the upper and rear sides of
the UPS.
Do not place the UPS in an enclosed space or put a cover the UPS.
●
Doing so may lead to an abnormal overheat or fire.
●
Temperature will increase inside the UPS and may cause a failure of the UPS and battery
deterioration.
●
Install the UPS 5cm away from the wall or further.
Do not use the UPS where the maximum temperature exceeds 40
°
C.
●
An battery deterioration will occur rapidly and may cause a fire.
●
Doing so may cause a failure or malfunction of the UPS.
Do not install or store the UPS in the places as listed below.
●
The humidity is lower than 10%. The humidity is higher than 85%. An enclosed space such as
a cabinet with no crevice. Near flammable gas and/or corrosive gas. Outdoors.
●
Doing so may cause a fire.
Do not connect devices that exceed the output capacity of the UPS.
You can add extra devices with a plug strip. Note that the plug strip does
not permit to plug in the device, which exceeds the current capacity of
the plug strip.
●
The UPS may detect overload and stop the output.
●
The plug strip cord may heat up and could lead to a fire.
Do not install the UPS in the other orientations.
Do not install the UPS on a structurally unsound base.
●
See "2-2 Installing" on page 12.
●
Toppling and dropping may cause injury.