6-3
Replacing the Fan Unit
This section describes how to replace the Fan Unit, a part of the NX7-series CPU Unit that allows
replacement as preventive maintenance.
A CPU that is incorporated in an NX7-series CPU Unit requires forced cooling to maintain its perfor-
mance. A Fan Unit is used to cool the CPU.
If the Fan Unit is not mounted, or if rotation of the fan stops or the rotation speed decreases due to a
failure or other causes, a
Slow Fan
error occurs in the Controller. If you continue the operation without
taking measures, a
CPU Unit Overheat
error (a minor fault level Controller error) or a
CPU Unit Over-
heat
(Operation Stopped) error may occur. The latter will stop operation of the Controller.
The Fan Unit has a high resistance to wear and a long service life that corresponds to the life of an
NX7-series CPU Unit. However, an accidental failure may be caused by entry of foreign particles or
other factors.
The NX7-series CPU Units employ a replaceable Fan Unit that allows preventative maintenance.
You need to replace the Fan Unit if the Fan Unit stops or a
Slow Fan
error occurs and operation is not
recovered after you remove the obstacle from the Fan Unit.
When you replace the Fan Unit, stop the operation and turn OFF the power supply to the Controller.
Use an NX-FAN01 Fan Unit.
The service life of a Fan Unit is 10 years at the ambient temperature of 55°C, and the storage limitation
for a Fan Unit that is not energized is 1 year.
Select a Fan Unit which was manufactured less than 10 years ago and has been stored for less than a
year without being energized. Perform operation check for the Fan Unit before you use it in normal
operation.
Precautions for Correct Use
• Do not use a Fan Unit which was subject to a strong impact, such as dropping on the floor. A
damaged bearing may cause a failure.
• Perform periodic cleaning procedures and remove dust from the Fan Unit. The service life of
the Fan Unit may be reduced due to dust.
6-3-1
Purpose of Attaching the Fan Unit
6-3-2
Fan Unit Replacement Period
6-3-3
Fan Unit Used for Replacement
Содержание NX701-1620
Страница 11: ...9 Manual Structure NX series CPU Unit Hardware User s Manual W535...
Страница 46: ...Sections in this Manual 44 NX series CPU Unit Hardware User s Manual W535...
Страница 64: ...1 Introduction to NX series Controllers 1 18 NX series CPU Unit Hardware User s Manual W535...
Страница 72: ...2 System Configuration 2 8 NX series CPU Unit Hardware User s Manual W535...
Страница 90: ...3 Configuration Units 3 18 NX series CPU Unit Hardware User s Manual W535...
Страница 156: ...6 Inspection and Maintenance 6 14 NX series CPU Unit Hardware User s Manual W535...
Страница 163: ...I 1 I NX series CPU Unit Hardware User s Manual W535 Index...
Страница 166: ...I 4 NX series CPU Unit Hardware User s Manual W535 Index...
Страница 167: ......