Precautions for Correct Use
Tighten terminal block screws and cable screws to the following torques.
Terminal Screws
M4: 1.2 N·m
M3: 0.5 N·m
Cable Connector Screws
M2.6: 0.2 N·m
Routing Wiring Ducts
Install the wiring ducts at least 20 mm away from the tops of the Rack and any other objects (e.g.,
ceiling, wiring ducts, structural supports, devices, etc.) to provide enough space for air circulation
and replacement of Units.
Breakers,
fuses
Power
equipment
such as
transformers
and magnetic
relays
Terminal blocks for
power equipment
Terminal blocks
for PLC
Fuses, relays, timers, etc.
(Do not install devices that
generate heat or power
equipment.)
NX-series
Controller
Input duct
Output duct
200 mm min.
Power duct
EtherCAT
Slave Terminal, etc.
Содержание NX701-1620
Страница 11: ...9 Manual Structure NX series CPU Unit Hardware User s Manual W535...
Страница 46: ...Sections in this Manual 44 NX series CPU Unit Hardware User s Manual W535...
Страница 64: ...1 Introduction to NX series Controllers 1 18 NX series CPU Unit Hardware User s Manual W535...
Страница 72: ...2 System Configuration 2 8 NX series CPU Unit Hardware User s Manual W535...
Страница 90: ...3 Configuration Units 3 18 NX series CPU Unit Hardware User s Manual W535...
Страница 156: ...6 Inspection and Maintenance 6 14 NX series CPU Unit Hardware User s Manual W535...
Страница 163: ...I 1 I NX series CPU Unit Hardware User s Manual W535 Index...
Страница 166: ...I 4 NX series CPU Unit Hardware User s Manual W535 Index...
Страница 167: ......