4 - 83
4 Safety Function Blocks
NX-series Safety Control Unit Instructions Reference Manual (Z931)
4
SF
_Muting
P
a
r_2Sensor
• Muting is used to intentionally disable a safety function. Muting is used, for example, to pass a work-
piece through a hazardous area without stopping the machine. Muting is activated by muting sen-
sors. Two muting sensors are used. To correctly incorporate the safety function into a manufacturing
process, you must ensure that people will not enter the hazardous area while the light curtain is being
muted. Pushbuttons, proximity sensors, photoelectric barriers, limit switches, and other devices that
do not have failsafe mechanisms are used for muting sensors. Muting operation must be indicated by
indicator lights.
• There are two types of muting: parallel and sequential. This FB performs parallel muting with two
muting sensors. An application example is provided below. (Refer to
tion Application Example with Two Reflective Light Barriers
.
) The sensors must be
located as described in
Annex F.7
in
CD 2005
of
IEC 62046,
as shown in the application example.
The FB can be used for either forward or backward passage. However, the actual direction cannot be
identified. To prevent manual operation, muting must also be enabled by process control with the
MutingEnable
signal to perform muting.
• The input parameters to the FB include two muting sensor signals (
S_MutingSwitch11
and
S_MutingSwitch12
), an OSSD signal from a photoelectric protection device (
S_AOPD_In
), and two
time parameters (
DiscTimeEntry
and
MaxMutingTime
).
• Activate the
S_StartReset
input only when you can ensure that no hazardous state will occur as the
result of starting the Safety CPU Unit.
MutingEnable
BOOL
TRUE or FALSE
FALSE
A constant or a variable. It is a command from the control
system to enable starting muting as required in the
machine cycle. You can change this signal to OFF after
muting starts.
FALSE: Disables muting.
TRUE: Enables starting muting.
S_StartReset
SAFEBOOL TRUE or FALSE
FALSE
Safety FB Common Input Variables
Reset
BOOL
TRUE or FALSE
FALSE
Refer to
Safety FB Common Input Variables
Output Variables
Variable
Data type
Valid range
Default
Description
Ready
BOOL
TRUE or FALSE
FALSE
Refer to
Safety FB Common Output Variables
S_AOPD_Out
SAFEBOOL TRUE or FALSE
FALSE
This safety output gives the status of the protection
devices that is being muted.
FALSE: Something has entered the AOPD protected area
and muting is disabled.
TRUE: Nothing has entered the AOPD protected area and
muting is enabled.
S_MutingActive
SAFEBOOL TRUE or FALSE
FALSE
Gives the muting status.
FALSE: Muting is disabled.
TRUE: Muting is enabled.
Error
BOOL
TRUE or FALSE
FALSE
Safety FB Common Output Variables
4-4.
DiagCode
WORD
Depends on state
code.
16#0000
Refer to
Safety FB Common Output Variables
4-4.
Function
Variable
Data type
Valid range
Default
Description
Содержание NX-SL series
Страница 8: ...CONTENTS 6 NX series Safety Control Unit Instructions Reference Manual Z931 ...
Страница 14: ...Terms and Conditions Agreement 12 NX series Safety Control Unit Instructions Reference Manual Z931 ...
Страница 28: ...Sections in this Manual 26 NX series Safety Control Unit Instructions Reference Manual Z931 ...
Страница 98: ...2 Standard Functions 2 64 NX series Safety Control Unit Instructions Reference Manual Z931 ...
Страница 104: ...2 Standard Functions 2 70 NX series Safety Control Unit Instructions Reference Manual Z931 ...
Страница 110: ...2 Standard Functions 2 76 NX series Safety Control Unit Instructions Reference Manual Z931 ...
Страница 130: ...3 Safety Standard Function Blocks 3 20 NX series Safety Control Unit Instructions Reference Manual Z931 ...
Страница 265: ...I 1 I NX series Safety Control Unit Instructions Reference Manual Z931 Index ...
Страница 268: ...I 4 NX series Safety Control Unit Instructions Reference Manual Z931 Index ...
Страница 269: ......