47
Connection to a PC by the NT Link (1:1)
Section 2-5
2-5-3
PC Switch Settings
When the NT20S and PC are connected to each other, set the conditions at the PC
CPU so as to enable the NT link communications.
The following is a general description of switch settings.
S
C-series C200HS, C200HX/HG/HE, CPM1, CQM1
Set the operating conditions to the PC system setting area when a C200HS,
C200HX/HG/HE, CPM1 or CQM1 CPU is connected to the NT20S. The PC sys-
tem setting area (data memory) can be directly accessed from the peripheral
tool (LSS etc.).
The following describes the switch settings so as to enable the PC system set-
tings. For the details of the operation with the PC system setting area, refer to the
manual for the PC you are using.
[Switch setting] (C200HX/HG/HE, CQM1)
S
RS-232C port communication
condition settings
Set DIP switch 5 to OFF (right side)
to enable setting of the PC system
settings.
ON
↔
OFF
DIP switch settings
123456
ON
[PC system setting area settings] (C200HX/HG/HE, CPM1, CQM1)
Write values to the PC system setting area (data memory) in accordance with the
CPU unit port used for connection to the NT20S.
PC Side
Channel #
Writing Value
Settings
RS-232 port of
C200HX/HG/HE,
CQM1
DM6645
Port A of C200HX/
HG/HE
DM6555
4000
Use NT link (1:1)
Port B of C200HX/
HG/HE
DM6550
CPM1
DM6650
Содержание NT20S
Страница 1: ...Cat No V020 E1 04 NT20S Programmable Terminal OPERATION MANUAL ...
Страница 2: ...i ...
Страница 3: ...ii ...
Страница 4: ...iii NT series Programmable Terminal Operation Manual Revised August 1997 ...
Страница 5: ...iv ...
Страница 7: ...vi ...
Страница 11: ...x ...
Страница 19: ...xviii ...
Страница 129: ...110 ...
Страница 169: ...150 ...
Страница 253: ...234 ...