183
Lamps, Touch Switches, Numeral Setting
Section 5-3
5-3-4
Lit (Flashing) and Unlit Touch Switch Statuses
(Changing the Status of Allocated Bits)
This section describes how to change the statuses of allocated bits and thereby
the statuses of the touch switches displayed by the NT20S.
The statuses of touch switches displayed by the NT20S are changed by switching
the control bits allocated in the PC memory ON and OFF.
NT20S
PC
Lit
1
1 (ON)
Allocated bit (touch switch #1)
Touch switch #1
The status of the lamp bit reflects the touch switch status, as follows:
0 (OFF):
Unlit
1 (ON):
Lit (inverse display) or flashing
Procedure
1. Use the support tool to allocate the touch switch lamp bits to the PC memory.
2. When creating the screen data using the support tool, register the touch
switch for a screen.
3. Create the PC program to switch the lamp bit of the touch switch ON and
OFF.
Set whether the lamp lights continuously or flashes when the bit comes ON
by setting the touch switch display attribute with the support tool.
5-3-5
Notifying the Host that a Switch has been Pressed
(Determining Touch Switch Status)
This section describes how the status of a touch switch (whether it has been
pressed or not) is ascertained.
With the NT20S, when a touch switch is pressed, the notify bit allocated to that
touch switch in the PC memory is automatically notified.
Touch switch #1
Allocated notify bit (touch switch #1)
NT20S
PC
1
Содержание NT20S
Страница 1: ...Cat No V020 E1 04 NT20S Programmable Terminal OPERATION MANUAL ...
Страница 2: ...i ...
Страница 3: ...ii ...
Страница 4: ...iii NT series Programmable Terminal Operation Manual Revised August 1997 ...
Страница 5: ...iv ...
Страница 7: ...vi ...
Страница 11: ...x ...
Страница 19: ...xviii ...
Страница 129: ...110 ...
Страница 169: ...150 ...
Страница 253: ...234 ...