236
Hardware Faults
Section 7-1
7-1
Hardware Faults
When a fault relating to the operation of the NT20S occurs, find the symptoms in
the table below and respond by following the corresponding “Remedy” indicated in
the table.
NT20S Symptoms
Cause
Remedy
POWER LED fails to
come ON
Power is not being supplied.
Check the connections and make sure that power is
supplied correctly.
(Refer to “2-2-3 Power Supply Connection”, page 29.)
Power supply fuse has blown
Contact your OMRON service center.
Nothing is displayed on
the screen (it is
completely white).
Screen #0 has been read at the host
side.
This is not an error. Change the screen number.
(Refer to “4-3 Screen Display”, page 122.)
Communication with the
support tool not possible.
The Transmit Mode has not been
established.
Display the system menu and select the Transmit
Mode.
(Refer to “3-6 Registering the Screen Data”, page 86.)
Not connected to the support tool.
Check the installation of the connector cable.
(Refer to “2-3 Connecting to the Support Tool”, page
31.)
The PT type/direct connection
settings made at the support tool do
not agree with the NT20S.
Make the PT type setting and direct connection setting
in the “tool settings” of the support tool agree with the
NT20S.
Cannot communicate with
the PC/Host.
Memory switch settings do not
match.
Check the communication setting in the “Memory
Switch” menu of the Maintenance Mode, and match
the PC and NT20S settings.
(Refer to “3-5 Setting the Conditions of
Communications with the PC/Host by Using the
Memory Switches”, page 75.)
NT20S and PC are not correctly
connected.
Check that the type, length and installation of the
connector cable match the specifications.
(Refer to “2-4 Connection to a PC by the Host Link”,
page 32, “2-5 Connection to a PC by the NT Link”,
page 45, and “2-8 Host Connections by RS-232C”,
page 63.)
When NT link (1:N), there is unit
number duplication.
Set again with no duplication.
Power not supplied to the NT20S,
PC, or host
Check the power supply.
Buzzer sounds, RUN LED
is OFF.
Malfunction due to external noise.
Distance the communication cable from the source of
the noise and insert a noise filter in the power supply
line.
Touch panel does not
respond
Malfunction due to external noise
Distance the communication cable from the source of
the noise and insert a noise filter in the power supply
line.
Touch panel is broken.
Check the touch panel by performing the touch panel
test in the I/O check in the maintenance mode.
PC mode changes to
monitor mode.
The NT20S changes the mode
during host link communication.
This is normal with the NT20S specification. When
using a PC that can also be connected using the NT
link, connect it with the NT link (the mode is not
changed when using the NT link).
Содержание NT20S
Страница 1: ...Cat No V020 E1 04 NT20S Programmable Terminal OPERATION MANUAL ...
Страница 2: ...i ...
Страница 3: ...ii ...
Страница 4: ...iii NT series Programmable Terminal Operation Manual Revised August 1997 ...
Страница 5: ...iv ...
Страница 7: ...vi ...
Страница 11: ...x ...
Страница 19: ...xviii ...
Страница 129: ...110 ...
Страница 169: ...150 ...
Страница 253: ...234 ...