![Omron NT11 - 01-2004 Скачать руководство пользователя страница 45](http://html.mh-extra.com/html/omron/nt11-01-2004/nt11-01-2004_user-manual_744535045.webp)
32
Connection to a PLC by the Host Link (RS-232C Type)
Section 2-4
PLC Setup Settings
When connecting to a C200HS, C200HX/HG/HE(-Z)E, CPM1, CPM2A,
CPM2C, CQM1, or CQM1H CPU Unit, or SRM1, set the following communi-
cation conditions for the PLC Setup.
*1 Set the Host Link baud rate at 9,600 bps or 19,200 bps with the memory
switch at the NT11. For details, refer to
Settings the Host Link Method
(page 74).
Set the PLC Setup settings directly from a Programming Device (e.g., the CX-
Programmer Support Software).
For details on operations relating to the PLC Setup, refer to the manual for the
PLC which is used.
The PLC Setup area word addresses and settings to be made depending on
the Unit and port to which the connection is made are shown below.
CPM2A, CPM2C, CQM1H, or SRM1: Peripheral port connection
CPM2A, SRM1
• Connect to the CPU Unit’s built-in RS-232C port.
• Connect to the peripheral port through a CPM1-CIF01 RS-
232C Adapter.
CPM2C
Connect to the CPU Unit’s RS-232C port or the peripheral
port through a Connecting Cable (CPM2C-CN111, CS1W-
CN118, or CS1W-CN114).
(The CPM2C-CN111 splits the Unit’s Communication Port
into a RS-232C port and a peripheral port. A CPM1-CIF01
RS-232C Adapter is also required to connect to this periph-
eral port.)
Item
Setting at Host
Communication mode
Host Link mode
Baud rate
Set the same speed as set at the NT11
(*1)
Stop bits
2 stop bits
Parity
Even
Data length
ASCII 7 bits
Unit #
00
Word
Writing Value
Settings
DM6650
0001
Host Link mode, no CTS control
Communication conditions set by the contents of DM
DM6651
0303
Data length 7 bits, 2 stop bits, even parity, baud rate:
9,600 bps
0304
Data length 7 bits, 2 stop bits, even parity, baud rate:
19,200 bps
DM6653
0000
Unit # 00
PLC model
Connection method
Содержание NT11 - 01-2004
Страница 1: ...USER S MANUAL Cat No V084 E1 01 NT11 Programmable Terminal ...
Страница 2: ...NT11 Programmable Terminal User s Manual Produced January 2004 ...
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 13: ...xiv Safety Precautions 3 ...
Страница 27: ...14 Before Operating Section 1 6 ...
Страница 71: ...58 Connecting a Printer Section 2 8 ...
Страница 119: ...106 Daily Report Display History Printing Function Section 4 10 ...
Страница 157: ...144 Inspection and Cleaning Section 6 3 ...
Страница 162: ...149 Appendix B Dimensions Body NT11 SF121 B EV1 38 2 7 5 218 203 113 98 ...
Страница 163: ...150 Dimensions Appendix B ...
Страница 165: ...152 Transporting and Storing the NT11 Appendix C ...
Страница 183: ...170 Revision History ...
Страница 186: ...NT11 Programmable Terminal Cat No V084 E1 01 USER S MANUAL ...