![Omron NT11 - 01-2004 Скачать руководство пользователя страница 127](http://html.mh-extra.com/html/omron/nt11-01-2004/nt11-01-2004_user-manual_744535127.webp)
114
Outline of Host Link/NT Link Operation
Section 5-2
*1 LR 00000 to LR 00199 are converted to CIO 01000 to CIO 01199.
*2 The EM Area is supported only by the C200HX/HG/HE (-Z)E PLCs.
The Auxiliary Area of the CVM1 and CV-series PLCs is allocated to system
functions, and it cannot be used for purposes other than system use.
The range of each memory area differs according to the PLC. Refer to
Appen-
dix D Making the Cable
on page 153.
Procedure
1.
Use the support tool to allocate the PT status notify area (PT to PLC) to
the PLC memory.
2.
Create a PLC program to read the “currently displayed screen word” in the
PT status notify area when the “screen switch strobe flag” in the PT status
notify area has turned ON.
Reference
• The contents of the “currently displayed screen word” are updated also by
switching the screen by using the menu screen function of the NT11.
• For details on the menu screen function, refer to
4-7 Menu Screen Func-
tion
(page 99).
Example of Reading the Number of Currently Display Screen
This example gives a PLC program that reads the screen number each time
the screen is switched. In this example, the number of the previous screen is
also stored.
• Support tool settings
Make the following settings with the support tool:
PT status notify area: Word 0110
• PLC ladder program
• Program operation
1.
When the NT11 screen display switches and the screen switch strobe flag
(bit 11212) turns ON, the contents of DM0100 are transferred to DM0101.
The number of the previously displayed screen is stored in word 0101.
2.
The new screen number notified by the NT11 is read and transferred to
DM0100. The number of the currently displayed screen is stored in
DM0100.
E
EM Area
*2
,
current bank
OK
EM Area,
current bank
Not for Host
Link
EM Area,
current bank
Not for Host
Link
E0_ to
EC_
---
---
---
---
EM Area,
EM banks 0 to C
Not for Host
Link
Symbol
C-series PLCs
Allocation
CV-series PLCs
Allocation
CS/CJ-series PLCs
Allocation
@MOV(21)
DM0100
DM0101
11212
@MOV(21)
110
DM0100
(1)
(2)
Word for storing a new screen number
Screen switch
strobe flag
Word for notifying the number of the currently displayed screen
Word for storing the number of the previous screen
Содержание NT11 - 01-2004
Страница 1: ...USER S MANUAL Cat No V084 E1 01 NT11 Programmable Terminal ...
Страница 2: ...NT11 Programmable Terminal User s Manual Produced January 2004 ...
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 13: ...xiv Safety Precautions 3 ...
Страница 27: ...14 Before Operating Section 1 6 ...
Страница 71: ...58 Connecting a Printer Section 2 8 ...
Страница 119: ...106 Daily Report Display History Printing Function Section 4 10 ...
Страница 157: ...144 Inspection and Cleaning Section 6 3 ...
Страница 162: ...149 Appendix B Dimensions Body NT11 SF121 B EV1 38 2 7 5 218 203 113 98 ...
Страница 163: ...150 Dimensions Appendix B ...
Страница 165: ...152 Transporting and Storing the NT11 Appendix C ...
Страница 183: ...170 Revision History ...
Страница 186: ...NT11 Programmable Terminal Cat No V084 E1 01 USER S MANUAL ...