5. Wiring
KP100L Quick Installation Guideline
19
(3)Use the rod terminal for AC wiring like the picture below when connected with KP100L.
wire Rod
terminal
(Phoenix Contact)
crimping pliers
(Phoenix Contact)
4 mm
2
AI 4-10 GY
CRIMFFOX 6, CRIMPFOX 10s
6 mm
2
AI 6-12 YE
CRIMFFOX 6, CRIMPFOX 10s
10 mm
2
AI 10-12 RD
CRIMPFOX 10s
(4) Insert wire in the interior of AC terminal block, and tighten by a minus driver.
(
Tightening torque :1.2 to1.8 N
⋅
m
)
The AC cable edge must use the one that pressure was put on to Rod terminal.
(5) Tighten the cap of the cable clamp surely.
When tightening the cable clamp is insufficient, the effect of the waterproof is not achieved.
■
Attachment of cover foreside R
Mount the cover foreside R by the 4screws surely(tightening torque : 1.5 to1.7N
⋅
m
)
When tightening the screws is insufficient, the effect of the waterproof is not achieved.
■
Connecting the Communication Cable and the AUX Cable
Refer to User’s manual for wiring of the communication cable and the AUX cable.
■
Options
The screw of hexagon (For Italy)
The customer who uses KP100L in Italy must buy the following screw. And, fix Cover foreside R
according to the following procedure. This is a requirements of ENEL Guideline.
Refer to User’s manual for detail installation.
DC SWITCH
It is necessary to use DC switch or circuit breaker which complies to the installation standard for
photovoltaic systems (VDE0100-712). When you install where you require the DC switch such as
Germany, please consult your OMRON representative
L1 L2 L3
N
PE
Rod terminal
12mm or more
Cut in 10mm