2 Design
2 - 26
Grid Connect Photovoltaic Inverte KP100L-OD-
USER’S MANUAL
5
Connect the Solar modules
High voltages exist when the Solar modules are exposed to
the sun. Exposed terminals of the Solar modules are live, and
can cause electric shock. Avoid making physical contact with
live parts of the device.
After the Solar modules are connected to KP100L, the input
voltage is greater than 200 VDC, the LCD displays the country
setting at first time operation.
Set a specified country. Refer to "3-2 Procedure at the First
Time Operation" for detail.
After the country setting, the input voltage is greater than 200
VDC and the AC grid is not connected to the KP100L, the LCD
displays.
Voltage measurement for each solar module string
Measurement confirmation: DC1 V
DC2 V
DC3 V
6
Grid voltage confirmation
Measure to confirm that the grid voltage is about 230 V.
Actual measurement: AC
(L1)
V
AC
(L2)
V
AC
(L3)
V
7
Power-ON delay time for
grid-connected operation
Step 1:
Check the connection between KP100L and AC Connection
System. And then check the connection between the Grid and
AC Connection unit.
Close the AC breaker or fuse in the unit.
Step 2
Measure the time until operation resumes.
Step 3
Confirm that the displays the status "Normal" and that the
KP100L performs the grid connect operation.
The KP100L is feeding power to the grid, and the green LED
displays.
8
Confirm the wattmeter
The Wattmeter installed to count the injected electricity should
work while the inverter displays that electricity is being
injected.
No.
Inspection Item
Procedure, Measurement or Confirmation
Checkmark
Fault E1-0
No Utility
Pac 1.5kW
0.50/0.50/0.50kW
Содержание KP100L-OD - 12-2010
Страница 18: ...17 Grid Connect Photovoltaic Inverte KP100L OD USER S MANUAL ...
Страница 21: ...20 Grid Connect Photovoltaic Inverte KP100L OD USER S MANUAL ...
Страница 33: ...1 Overview 1 12 Grid Connect Photovoltaic Inverte KP100L OD USER S MANUAL ...
Страница 63: ...2 Design 2 30 Grid Connect Photovoltaic Inverte KP100L OD USER S MANUAL ...
Страница 103: ...4 Maintenance Operations 4 12 Grid Connect Photovoltaic Inverter KP100L OD USER S MANUAL ...
Страница 113: ...6 After Sales Service 6 4 Grid Connect Photovoltaic Inverter KP100L OD USER S MANUAL ...
Страница 114: ...7 1 7 7 Grid Connect Photovoltaic Inverter KP100L OD USER S MANUAL 7 1 Standard Specification List 7 2 Specifications ...
Страница 117: ...7 Specifications 7 4 Grid Connect Photovoltaic Inverter KP100L OD USER S MANUAL ...
Страница 125: ...A Appendix A 8 Grid Connect Photovoltaic Inverter KP100L OD USER S MANUAL ...