2 - 17
2 Design
Grid Connect Photovoltaic Inverte KP100L-OD-
USER’S MANUAL
2-4 Wiring
2
(5)-2-2 Wiring when connecting 2 or more products
Connect the wire to 3: GO, 4: RS-) and 5: RS-485_DA(-) of the communication terminal
block(TB401). Connect the other wire to 6: GO, 7: RS-) and 8: RS-485_DA(-).
(5)-2-3 Terminal processing of wiring when connecting 2 or more products
Connect the other wire to 9: RS-485_END1 and 10: RS-485_END2. Be short-circuited.
Keep the voltage between GOof Communication terminal block and PE.is less than 50V.
1
2
3
4
5
6
7
8
9
10
1 2
3 4 5
6 7 8 9 10
RS-485_END2
RS-485_END1
1 2 3 4 5 6 7 8 9 10
KP100L
L1
L2
L3
N
PE
GO
GO
SG
RS-485 interface equipment
< 50V
Содержание KP100L-OD - 12-2010
Страница 18: ...17 Grid Connect Photovoltaic Inverte KP100L OD USER S MANUAL ...
Страница 21: ...20 Grid Connect Photovoltaic Inverte KP100L OD USER S MANUAL ...
Страница 33: ...1 Overview 1 12 Grid Connect Photovoltaic Inverte KP100L OD USER S MANUAL ...
Страница 63: ...2 Design 2 30 Grid Connect Photovoltaic Inverte KP100L OD USER S MANUAL ...
Страница 103: ...4 Maintenance Operations 4 12 Grid Connect Photovoltaic Inverter KP100L OD USER S MANUAL ...
Страница 113: ...6 After Sales Service 6 4 Grid Connect Photovoltaic Inverter KP100L OD USER S MANUAL ...
Страница 114: ...7 1 7 7 Grid Connect Photovoltaic Inverter KP100L OD USER S MANUAL 7 1 Standard Specification List 7 2 Specifications ...
Страница 117: ...7 Specifications 7 4 Grid Connect Photovoltaic Inverter KP100L OD USER S MANUAL ...
Страница 125: ...A Appendix A 8 Grid Connect Photovoltaic Inverter KP100L OD USER S MANUAL ...