64
Upper Limit (H) of Linear Output Range
Lower Limit (L) of Linear Output Range
Linear output setting is made in the option menu to enable the K3NP to have
voltage or current output in proportion to the change in display value.
·
The maximum and minimum values of linear output are set in this parameter.
Linear output
20 mA or 5 V
Display value
4 mA or 1 V
·
L can be greater or less than H.
·
L cannot be the same as H, otherwise H will be automatically set to a value
obtained by adding 1 to L.
·
The teaching function can be used for setting linear output ranges.
Setting range
Default
0 to 99999
H linear output range
99999
L linear output range
0
Refer to
6-1 Teaching Function
.
This setting is available for the K3NP with the Linear Output Board.
lset.h
lset.l
FUNCTION
SETTING
REFERENCE
MODELS
Setting Mode
Section 4-2