85
13. Press the Shift Key to select whether or not to accept the settings.
Set Value LED Display Model
Basic Model
14. Press the Up Key to select
yes
.
15. Press the Mode Key to overwrite all calibration data and to put the K3NH into
RUN mode. The calibration data will not be overwritten if
no
is selected.
Set Value LED Display Model
Basic Model
RUN mode
5-3-5 Temperature-resistance Thermometer Calibration
Preparation
•
Make sure that the thickness of each connected wire is the same.
•
Dial 6 in the following diagram represents a high-precision resistance box.
•
Short-circuit terminals 3 and 4 with each other.
Dial 6
100 to 240 VAC
12 to 24 VDC
Calibration
1, 2, 3...
1. First, the
sure
alarm display will appear. This will not appear once field cal-
ibration is performed.
Set Value LED Display Model
Basic Model
2. Press the Mode Key to display
p300
. The teaching indicator will be lit. Then
calibrate the main input.
Set Value LED Display Model
Basic Model
Maintenance Mode
Section 5-3