79
•
Only input set with the input type parameter in setup mode can be the object of
input calibration. Press the Mode Key for approximately one second to tenta-
tively register the parameter data of all calibration items.
•
The data registration setting
str
does not appear unless all calibration items
are tentatively registered.
Procedure for Field Calibration
1, 2, 3...
1. Press the Mode and Shift Keys simultaneously while turning the K3NH on to
display
mant
maintenance mode setting.
Set Value LED Display Model
Basic Model
2. Press the Mode Key for more than one second to display
reĆin
set value
initialization setting.
Set Value LED Display Model
Basic Model
3. Press the Mode Key to display the
calib
field calibration setting.
Set Value LED Display Model
Basic Model
4. Press the Shift Key to display
no
.
Set Value LED Display Model
Basic Model
5. Press the Up Key to display
yes
. Press the Mode Key to select the calibra-
tion item.
Set Value LED Display Model
Basic Model
User calibration
5-3-4 Thermocouple Calibration
•
There are two calibration methods. One applies to thermocouple group 1 (i.e.,
K1, J1, L1, E, N, W, and PL
II
) and the other applies to thermocouple group 2
(K2, J2, L2, R, S, B, T, and U).
Maintenance Mode
Section 5-3