2.2 Installation Method
16
2.2 Installation Method
Installation Method and Direction
• Install the SERVOPACK perpendicular to the wall. The SERVOPACK contains a built-in fan for cooling
and must be mounted in the specified direction.
• Connect the mounting holes securely to the mounting surface with M4 screws (two mounting holes).
Space between SERVOPACK Units
• Be sure to keep a space between adjacent SERVOPACK units if they are mounted inside the control
panel so that the units can be cooled.
• Do not cover the inlet or outlet parts and prevent any foreign objects, such as metalic fragment, or
combustibles from entering the product.
Failure to observe this caution may cause internal elements to deteriorate resulting in malfunction or
fire.
SERVOPACK installation plate
M4 screw
50 mm
min.
50 mm
min.
30 mm
min.
10 mm
min.
Air outlet direction
Air inlet direction