2-1-8. Configuring Initial Setup Data
Write address constant on the DM as follows.
DM20000=#2300
DM20002=#0005
DM20003=#0010
This unit performs initial setup through data exchange with Special I/O unit
assignment DM area of the CPU unit. To use temperature warning function, you must
configure warning mode and warning hysteresis settings here.
In this example, set DM20000 to 2300 (BCD: set Warning 1 of Loop 1 to upper limit
warning mode and Warning 2 to lower limit warning mode), DM20002 to 0005 (BCD:
Warning hysteresis of Warning 1 to 5 deg. C), and DM20003 to 0010 (BCD: Warning
hysteresis of Warning 2 to 10 deg. C).
Details of these setting items are described in the next page:
SYSMAC CJ Series
n x100
-
n x 100+99
Sending to each unit
automatically when
power is turned ON or
special I/O restart flag is
turned ON.
Temperature Control Unit
CJ1W-TC
[Initial setting data]
m=20000+100 x Unit No.
D
(m)
D
(m+1)
D
(m+2)
-
D
(m+9)
Loop 1and 2
Alarm mode setting
Loop 3 and 4 *1
Alarm mode setting
Loop 1 to 4 *1
Alarm hysteresis
setting
Allocated DM No.
Unit 0
Unit 1
Unit 2
Unit 3
Unit 4
Unit 5
Unit 6
Unit 7
Unit 8
Unit 9
-
-
Unit n
Unit 94
D20000 - 20099
D20100 - 20199
D20200 - 20299
D20300 - 20399
D20400 - 20499
D20500 - 20599
D20600 - 20699
D20700 - 20799
D20800 - 20899
D20900 - 20999
-
-
D29400 - 29499
[DM area for special I/O unit]
2-13 Temperature Control Unit
CJ1W-TC001/101/003/103/002/102/004/104
Содержание FB LIBRARY -
Страница 1: ......
Страница 14: ...2 1 Controller Link Unit CJ1W CLK21 V1...
Страница 23: ...2 2 DeviceNet Slave DRT2 Series DRT2...
Страница 31: ...2 3 Position Control Unit CJ1W NCF71...
Страница 42: ...2 4 Position Control Unit CJ1W NC113 133 213 233 413 433...
Страница 49: ...2 5 Position Control Unit CS1W NC113 133 213 233 413 433...
Страница 57: ...2 6 Inverter 3G3MV A2 AB A4 3G3RV A2 A4...
Страница 71: ...2 7 Servo Driver R88D WT WT H WT HL R7D AP H AP L...
Страница 84: ...2 8 RFID ID Sensor V600 H...
Страница 95: ...2 9 Vision Sensor F160 C10...
Страница 105: ...2 10 2D Code Reader V530 R2000 R160 R150V3...
Страница 118: ...2 11 Smart Sensor ZX SF11 ZX LD40 ZX LDA11 N...
Страница 129: ...2 12 Temperature Controller E5ZN 2...
Страница 139: ...2 13 Temperature Control Unit CJ1W TC001 101 003 103 002 102 004 104...
Страница 148: ...Chapter 3 OMRON FB Library List Folder Configuration of The OMRON FB Library List of The OMRON FB Library...
Страница 162: ...Cat No R123 E01 01 Note Specifications subject to change without notice Printed in Japan Authorized Distributor...