F3SP-U5P-TGR
User's manual
21
N.C.
A1
B1
S
A2
B2
d1
Muting sensor connection:
contact of A1
contact of A2
contact of B1
contact of B2
24 V
DC
F3SP-U5P-TGR
terminals
D
L
v
9
MUTE A
8
MUTE B
11
MUTE C
10
MUTE D
N.C.
The examples above are thought for the use of the muting functions only
relating to sensors S1 and S2, with the configuration
DIP-SWITCH
2 in the off
positions; sensors S1 and S2 are controlled by the
muting
A and B inputs,
while sensors S3 and S4 are controlled by the
muting
C and D inputs. His
configuration makes other applications be possible.
Application with eight
muting
sensors and output and input control
We imagine an area in which a manipulator acts; the barriers in input and
output must allow the passage of the packages only when the manipulator
has terminated its work, thus avoiding intrusions in unwished moments.
S3
S4
B4 A4 B3 A3
S1
S2
A2
B1 A1
Trigger zone
of handler
B2