where:
D:
minimum distance that the
muting
sensors keep active the
request; it depends on the parcel length: D < L.
d
1
:
necessary maximum distance so that the muting request is
accepted; it depends on the parcel speed:
d
max
[cm]= v[m/s] * 3[s] * 100
This distance must not allow to activate both sensors and
the
muting
with the accidental passage of a person.
Application with four muting sensors and only photocell S1:
Power cable
Light cable
Muting cable
RX cable
TX cable
Muting
signalizer
Start & Test
button
Protect the
cables
F3SP-U5P-TGR
control-unit
Содержание F3SP-U5P