14
Section 5:
Alignment Procedure
After completing correct mechanical assembly and connections, as described in the previous sections, the
SLC should be aligned as follows:
•
Disconnect the SLC's power supply.
•
Open the test/restart contact.
•
Restore the SLC's power supply.
•
Adjust the direction of the SLC by moving the transceiver or the mirror. The 2 yellow LEDs located on
the transceiver will both be lit when the SLC is aligned correctly. In addiction also the green guard LED
will switch on and the red break LED will switch off
•
After aligning the SLC, secure the bolts firmly.
•
Disconnect the power supply.
•
Restore the SLC's power supply (with the test contact closed); it will enter operating mode.
•
Complete all the tests described in section 9 (final checks) and those required for routine maintenance
(section 10).