SETTING LIST
E5EK
A--9
Mode
Parameter Name
Setting Range
Unit
Default
Remarks
Setting
Remote/Local
RMT/LCL
None
LCL
Standby time
0.00 to 99.59
Hour,
Min.
0.00
LBA detection time
0 to 9999
Sec
0
MV at reset
-5.0 to 105.0
%
0.0
MV at PV error
-5.0 to 105.0
%
0.0
MV upper limit
MV lower limit +0.1 to 105.0
%
105.0
MV lower limit
-5.0 to MV upper limit -0.1
%
-5.0
Level 2
MV change rate limitter
0.0 to 100.0
%FS
0.0
Input digital filter
0 to 9999
sec
0
Open/close hysteresis
0.1 to 20.0
%
0.8
Alarm 1 hysteresis
0.01 to 99.99
%FS
0.02
Alarm 2 hysteresis
0.01 to 99.99
%FS
0.02
Alarm 3 hysteresis
0.01 to 99.99
%FS
0.02
Input shift upper limit
-199.9 to 999.9
°
C/
°
F
0.0
Temperature input
Input shift lower limit
-199.9 to 999.9
°
C/
°
F
0.0
Temperature input
Input type
0 to 21
None
2
Scaling upper limit
Scaling lower limit +1 to 9999
None
100
Analog input
Scaling lower limit
-1999 to scaling upper limit -1
None
0
Analog input
Decimal point
0 to 3
None
0
Analog input
_
C/
_
F selection
_
C/
_
F
None
_
C
Temperature input
Parameter initialize
Yes/No
None
NO
Control output 1 assignment
*7
None
HEAT
Control output 2 assignment
*7
None
AL-1
Auxiliary output 1 assignment
*8
None
AL-2
S t
Auxiliary output 2 assignment
*8
None
AL-3
Setup
Alarm 1 type
1 to 11
None
2
Output assignment
needed
Alarm 1 open in alarm
N-O/N-C
None
N-O
Output assignment
needed
Alarm 2 type
1 to 11
None
2
Output assignment
needed
Alarm 2 open in alarm
N-O/N-C
None
N-O
Output assignment
needed
Alarm 3 type
1 to 11
None
2
Output assignment
needed
Alarm 3 open in alarm
N-O/N-C
None
N-O
Output assignment
needed
Direct/Reverse operation
OR-R/OR-D
None
OR-R
*1 During heating and cooling control, the lower limit becomes -105.0%
*2 Use “Program List” (page A-11) for the setting value of each step.
*3 EU/time unit of ramp rate
*4 Program time unit
*5 During heating and cooling control, the setting range becomes 0.0 to 105.0%.
*6 During heating and cooling control, the setting range becomes -105.0 to 0.0%.
*7 HEAT/COOL/AL-1/AL-2/AL-3/HBA/LBA/TS-1/TS-2/P.END/STG
*8 AL-1/AL-2/AL-3/HBA/LBA/TS-1/TS-2/P.END/STG/S.ERR/E333
*1
*2
*5
*6
Содержание E5EK
Страница 1: ...User s Manual Cat No H089 E1 02 Digital Controller Programmable Type...
Страница 24: ...CHAPTER 1 INTRODUCTION 1 14...
Страница 36: ...CHAPTER 2 PREPARATIONS 2 12...
Страница 162: ...CHAPTER 6 USING THE COMMUNICATIONS FUNCTION 6 20...
Страница 176: ...CHAPTER 7 CALIBRATION 7 14...
Страница 193: ...SETTING LIST A 11...