6.6 Program Example
E5EK
6--19
J
Examples of use
•
Set the unit No. to “00”.
•
In the following examples, data is shown in individual blocks to make the exam-
ples easier to understand. However, when actually creating programs, do not leave
spaces between frame items. Also, response are displayed without spaces between
frame items.
F
Set the set point to “300.0”
•
Input data
@ 00 5 05 3000
300.0
Set point
Write parameter
•
Response
@ 00 5 05 00 3000 (FCS) *
Normal end
F
Start running
•
Input data
@ 00 3 00 0000
Run
Run/Reset
Special command
•
Response
@ 00 3 00 00 0000 (FCS) *
Normal end
F
Monitor process value
•
Input data
@ 00 1 00 0000
Dummy data
Monitor process value
Read parameter
•
Response
@ 00 1 00 00 2000 (FCS) *
Process value = 2000
Normal end