E5EK
5--23
Heater current monitor
Conditions of Use
The HBA output function must be
assigned as the output.
•
Measures the current value of the heater from CT input.
•
This parameter is not displayed when the linear output unit (E53-C
V
, E53-V
V
) is
mounted.
Monitor Range
Unit
0.0 to 55.0
A
•
[
] is displayed when 55.0 A is exceeded.
F
Related description
4.9 How to Use the Heater Burnout Alarm (page 4-23)
F
Related parameters
“Heater burnout” (level 1 mode)
“HBA latch” (option mode)
E5EK-TAA2
Heater burnout
Conditions of Use
The HBA output function must be
assigned as the output
•
Outputs the heater burnout alarm when the heater current value falls below this
parameter setting.
•
When the set value is “0.0”, the heater burnout alarm is “OFF”. When the set
value is “50.0”, the heater burnout alarm is “ON”.
Setting Range
Unit
Default
0.0 to 50.0
A
0.0
F
Related description
4.9 How to Use the Heater Burnout Alarm (page 4-23)
F
Related parameters
“Heater current monitor” (level 1 mode)
“HBA latch” (option mode)
E5EK-TAA2
Level 1 Mode
Function
Monitor
See
Model
Function
Setting
See
Model