Temperature Controllers

 E5CSV

3

Installation

All models in the E5CSV Series conform to DIN 43700 standards.

The recommended panel thickness is 1 to 4 mm.

Be sure to mount the E5CSV horizontally.

Mounting the E5CSV

1.

For waterproof mounting, waterproof packing must be installed on the Controller. Waterproofing is not possible when group mounting several 

Controllers.

2.

Insert the E5CSV into the mounting hole in the panel.

3.

Push the adapter from the terminals up to the panel, and temporarily fasten the E5CSV.

4.

Tighten the two fastening screws on the adapter. Alternately tighten the two screws little by little to maintain a balance. Tighten the screws to a 

torque of 0.29 to 0.39 N·m.

Dimensions

Note:

All units are in millimeters unless otherwise indicated.

Controller

Terminal Cover

Note: 1.

The voltage output (12 VDC, 21 mA) is not electrically isolated from the internal circuits. When using a grounding thermocouple, do not 

connect output terminals 1 or 2 to ground. Otherwise, unwanted current paths will cause measurement errors.

2.

Models with 100 to 240 VAC and 24 VAC/VDC are separate. Models using 24 VDC have no polarity.

Panel Cutout Dimensions

44.8

×

44.8

84

78

6

48

×

48

60 min.

L = (48 

×

 N

2.5)

+1

  0

Mounting side-by-side

(group mounting of N Controllers)

45

+0.6

  0

45

+0.6

  0

45

+0.6

  0

L

Tightening

screws

48

76.5

7.5

Adapter for flush mounting

Panel

Y92F-30 Adapter for flush mounting

58

E5CSV

Note: 1.

The recommended panel thickness is 1 to 4 mm.

2.

Group mounting is possible in one direction only.

Note:

Terminals cannot be removed.

Hard Protective Cover

The Y92A-48B Protective Cover (hard type) is 

available for the following applications.

To protect the set from dust and dirt.

To prevent the panel from being accidentally 

touched causing displacement of set values.

To provide effective protection against water 

droplets.

°

C

92A-48B

92A-48B

8

9

10

7

6

3

4

5

2

1

1

2

1

2

3

4

5

12 VDC, 

21 mA

Alarm output

Alarm output 1

Relay output 

models

Voltage output 

models

(See note 1.)

Thermocouple/

platinum resistance thermometer multi-input

100 to 240 VAC, 50/60 Hz 

(24 VAC/VDC) 

(See note 2.)

A

B

B

Thermocouple

input

Relay output

Voltage output

Platinum resistance 

thermometer input

48

48.8

22

9.1

E53-COV10

4

Temperature Controllers

E5CSV

Operation

E5CSV

Settings before Turning ON the Power

E5CSV

Remove the E5CSV from the case to make the settings.

1.

Insert the tool into the two tool insertion holes (one on the top and 

one on the bottom) and release the hooks.

2.

Insert the tool in the gap between the front panel and rear case, 

and pull out the front panel slightly. Grip the front panel and pull 

out fully. Be sure not to impose excessive force on the panel.

3.

When inserting the E5CSV, check to make sure that the sealing 

rubber is in place and push the E5CSV toward the rear case until 

it snaps into position. While pushing the E5CSV into place, push 

down on the hooks on the top and bottom surfaces of the rear 

case so that the hooks are securely locked in place. Make sure 

that electronic components do not come into contact with the 

case.

Note: 1.

The INIT switch is always OFF during normal operation.

Deviation indicators

The      indicator lights when the PV is greater than 
the SP and the     indicator lights when the PV is 
less than the SP.  The      indicator (green) lights 
when the deviation is less than 1% FS (0.25% FS 
for multi-input models). These indicators flash 
during ST (self-tuning)/AT (auto-tuning).

Mode indicators

The SP indicator lights when the setting 
temperature is being displayed. The ALM 
indicator lights when the alarm value 1 is 
being displayed.

PV, SP, Alarm Value, Input Shift Display

Alarm indicators

ALM1 (Alarm 1): Lights when the alarm 1 

output is ON.

ALM2 (Alarm 2): For future use.

Up Key

Pressing the Up Key increases the 
SP/alarm value display. Keeping the Up 
Key pressed continues to increase the 
display value. When the internal protect 
switch is ON, press the Up Key while 
holding down the Lock Release Key.

Output indicator

Lights when the control output is ON.

The display switches each time the  
       Key is pressed.

Lock Release Key

When the protect switch is ON, the set 
value can be changed by pressing the Up 
and Down Keys while holding down the 
Lock Release Key.

Down Key

Pressing the Down Key decreases the 
SP/alarm value display. Keeping the Down 
Key pressed continues to decrease the 
display value. When the internal protect 
switch is ON, press the Down Key while 
holding down the Lock Release Key.

When the power is turned ON, normally the 
display will use the display items in the following 
order each time the Mode Key is pressed.

Mode Key

PV

SP

Alarm value 1

Input shift value

Power ON

Press the       Key.

Press the       Key.

Press the       Key.

Press the       Key.

This item is not displayed when 
the Control Mode Switch 4 is OFF.

Flat-blade screwdriver 

(Unit: mm)

(1)

(1)

(2)

(3)

Tool insertion hole

0.4

2.0

20 min.

P

ON

X

1

2

3

4

5

6

Alarm  mode  switch  (See  note  1.)

Temperature range switch 

Control mode switches

INIT  switch 

(See  note  2.)

Protect switch

ON

7

Temperature Controllers E5CSV

Содержание E5CSV -

Страница 1: ...Advanced Industrial Automation Perfect control Enhanced functionality Easy setting up E5CSV temperature controller Ready set g o ...

Страница 2: ...mperature control in 4 simple steps The E5CSV temperature controller series is the enhanced successor to our E5CS series the most widely sold temperature controller that has established itself throughout the world as the ideal choice for simple cost effective temperature control P SV protection SW1 ON OFF PID control SW2 fast or slow process SW3 Heat or Cool SW4 Input shift ON OFF SW5 Thermocouple...

Страница 3: ...e control requirements with only 4 models No expert knowledge needed to optimise performance because of Self and Auto Tuning functions Reduced chance of malfunction thanks to set value protection End user friendly since the menu only has 3 parameters Excellent legibility with a large 13 5 mm single line 3 5 digit 7 segment LED display Clear status overview thanks to PV SV deviation indicator outpu...

Страница 4: ...er of alarms 1 1 alarm 3 Input type T Thermocouple platinum resistance thermometer multi input 4 Power supply voltage Blank 100 to 240 VAC D 24 VAC VDC 5 Terminal cover 500 Finger protection cover Ordering Information List of Models Accessories Order Separately Protective Front Cover 1 2 3 4 5 E5CSV 1T 500 Size Power supply voltage Number of alarm points Control output TC Pt multi input Incl termi...

Страница 5: ...uence of voltage Hysteresis for ON OFF control 0 1 FS Proportional band P 1 to 999 C automatic adjustment using auto tuning self tuning Integral time I 1 to 1 999 s automatic adjustment using auto tuning self tuning Derivative time D 1 to 1 999 s automatic adjustment using auto tuning self tuning Alarm output range Absolute value alarm Same as the control range Other 0 to 100 FS Alarm hysteresis 0...

Страница 6: ...ause measurement errors 2 Models with 100 to 240 VAC and 24 VAC VDC are separate Models using 24 VDC have no polarity Panel Cutout Dimensions 44 8 44 8 84 78 6 48 48 60 min L 48 N 2 5 1 0 Mounting side by side group mounting of N Controllers 45 0 6 0 45 0 6 0 45 0 6 0 L Tightening screws 48 76 5 7 5 Adapter for flush mounting Panel Y92F 30 Adapter for flush mounting 58 E5CSV Note 1 The recommended...

Страница 7: ...d The ALM indicator lights when the alarm value 1 is being displayed PV SP Alarm Value Input Shift Display Alarm indicators ALM1 Alarm 1 Lights when the alarm 1 output is ON ALM2 Alarm 2 For future use Up Key Pressing the Up Key increases the SP alarm value display Keeping the Up Key pressed continues to increase the display value When the internal protect switch is ON press the Up Key while holdi...

Страница 8: ...100 0 100 1 700 1 300 1 300 850 850 400 400 199 9 199 9 199 9 0 0 0 0 0 0 0 99 99 99 99 99 99 Setting number 0 1 2 3 4 5 6 7 8 9 Input Pt100 JPt100 SP range 1 000 900 800 700 600 500 400 300 200 100 0 100 850 500 400 400 199 9 200 199 9 200 99 99 0 0 0 0 0 0 0 0 99 99 99 99 Setting number 0 1 2 3 4 5 6 7 8 9 Mode Key Display Order If the SP falls outside the temperature range when the temperature ...

Страница 9: ... ON OFF PID PID control ON ON OFF control OFF Control period 2 s ON 20 s OFF Direct reverse opera tion Direct operation cooling ON Reverse operation heating OFF Input shift display Enabled ON Disabled OFF Tempera ture Sensor selection Platinum resistance thermometer input ON Thermocouple input OFF Temper ature unit F ON C OFF 6 5 4 3 2 1 ON 6 5 4 3 2 1 ON Set value Alarm type Alarm output operatio...

Страница 10: ...or Switch 2 OFF control period 20 s Quick Control Response Using an SSR Switch 2 ON control period 2 s 2 Set direct reverse operation for the output Performing Heating Control for Heaters Switch 3 OFF Performing Cooling Control for Freezers Switch 3 ON 6 5 4 3 2 1 ON Switch 1 OFF ON OFF control OFF ON Control output SP 6 5 4 3 2 1 ON OFF ON Control output SP 6 5 4 3 2 1 ON Switch 1 ON PID control ...

Страница 11: ...input shift set the input shift value to h0 The shift range depends on the setting unit 5 Protect Switch When the protect switch is ON Up Key and Down Key operations are prohibited to prevent setting mistakes 6 5 4 3 2 1 ON Multi input Thermocouple Platinum Resistance Thermometer Control mode switch 5 OFF Multi input Thermocouple Platinum Resistance Thermometer Control mode switch 5 ON Set ting F ...

Страница 12: ...ystems Programmable logic controllers Human machine interfaces Remote I O Motion Drives Motion controllers Servo systems Inverters Control Components Temperature controllers Power supplies Timers Counters Programmable relays Digital panel indicators Electromechanical relays Monitoring products Solid state relays Limit switches Pushbutton switches Low voltage switch gear Sensing Safety Photoelectri...

Отзывы: