background image

Temperature Controllers

 E5CSV

7

4. Using the Control Mode Switches

(1) Using ON/OFF Control and PID Control

(1.1) ON/OFF Control

The control mode is set to ON/OFF control as the default setting.

To perform cooling control of freezers, etc., turn ON switch 3.

(1.2) PID Control

Turn ON switch 1 to use PID control.

1. Set the control period.

Performing Control via Relay Output, External Relay, or 

Conductor

Switch 2: OFF (control period: 20 s)

Quick Control Response Using an SSR

Switch 2: ON (control period: 2 s)

2. Set direct/reverse operation for the output.

Performing Heating Control for Heaters

Switch 3: OFF

Performing Cooling Control for Freezers

Switch 3: ON

6

5

4

3

2

1

ON

Switch 1 OFF: ON/OFF control

OFF

ON

Control output

SP

6

5

4

3

2

1

ON

OFF

ON

Control output

SP

6

5

4

3

2

1

ON

Switch 1 ON: PID control

6

5

4

3

2

1

ON

OFF

ON

Control output

20 s

6

5

4

3

2

1

ON

OFF

ON

Control output

2 s

6

5

4

3

2

1

ON

0%

100%

SP

Output level

6

5

4

3

2

1

ON

0%

100%

SP

Output level

8

Temperature Controllers

E5CSV

(2) Using the E5CSV in Devices for Fahrenheit-scale Users

(Displaying in 

°

F)

Turn ON switch 6 to display temperatures in 

°

F.

Temperature Range for 

°

F

The temperature is set to 

°

F using the same temperature range switch as 

°

C.

Note:

The control range for multi-input (thermocouple/platinum resistance thermometer) models is -40 to +40

°

F of each temperature range. 

The previous name J-DIN has been changed to L in accordance with revisions to DIN standards.

(3) Setting Input Shift

Turn ON switch 4, and after turning ON the power, press the Mode 

Key until 

h0

 (indicates input shift of 0) is displayed. Press the Up and 

Down Keys to set the shift value.

Shift Example

Note:

When control mode switch 4 is turned OFF (no input shift 

display), the input shift is not displayed but the shift value is 

enabled. To disable input shift, set the input shift value to 

h0

.

The shift range depends on the setting unit.

5. Protect Switch

When the protect switch is ON, Up Key and Down Key operations are prohibited to prevent setting mistakes.

6

5

4

3

2

1

ON

Multi-input (Thermocouple/

Platinum Resistance 

Thermometer)

Control mode switch 5: OFF

Multi-input (Thermocouple/

Platinum Resistance 

Thermometer)

Control mode switch 5: ON

Set-

ting

°

F

Set-

ting

°

F

0

K

-99 to 1999

0

Pt100

-99 to 1500

1

0.0 to 199.9

1

0.0 to 199.9

2

J

-99 to 1500

2

-99 to 99

3

0.0 to 199.9

3

0 to 200

4

L

-99 to 1500

4

0 to 400

5

T

-99 to 700

5

JPt100 -99 to 900

6

0.0 to 199.9

6

0.0 to 199.9

7

U

-99 to 700

7

-99 to 99

8

N

-99 to 1999

8

0 to 200

9

R

0 to 1999

9

0 to 400

6

5

4

3

2

1

ON

Input shift display

Measured temperature

Temperature 

display

h0

 (no shift)

100

°

C

100

°

C

h9

 (+9

°

C shift)

100

°

C

109

°

C

l9

 (-9

°

C shift)

100

°

C

91

°

C

Setting unit

1

°

C

0.1

°

C

Compensation range

-99 to +99

°

C -9.9 to +9.9

°

C

Input shift display

L99 to H99

L9.9 to H9.9

P

ON

X

1

2

3

4

5

6

Protect Switch

Temperature Controllers E5CSV

11

Содержание E5CSV -

Страница 1: ...Advanced Industrial Automation Perfect control Enhanced functionality Easy setting up E5CSV temperature controller Ready set g o ...

Страница 2: ...mperature control in 4 simple steps The E5CSV temperature controller series is the enhanced successor to our E5CS series the most widely sold temperature controller that has established itself throughout the world as the ideal choice for simple cost effective temperature control P SV protection SW1 ON OFF PID control SW2 fast or slow process SW3 Heat or Cool SW4 Input shift ON OFF SW5 Thermocouple...

Страница 3: ...e control requirements with only 4 models No expert knowledge needed to optimise performance because of Self and Auto Tuning functions Reduced chance of malfunction thanks to set value protection End user friendly since the menu only has 3 parameters Excellent legibility with a large 13 5 mm single line 3 5 digit 7 segment LED display Clear status overview thanks to PV SV deviation indicator outpu...

Страница 4: ...er of alarms 1 1 alarm 3 Input type T Thermocouple platinum resistance thermometer multi input 4 Power supply voltage Blank 100 to 240 VAC D 24 VAC VDC 5 Terminal cover 500 Finger protection cover Ordering Information List of Models Accessories Order Separately Protective Front Cover 1 2 3 4 5 E5CSV 1T 500 Size Power supply voltage Number of alarm points Control output TC Pt multi input Incl termi...

Страница 5: ...uence of voltage Hysteresis for ON OFF control 0 1 FS Proportional band P 1 to 999 C automatic adjustment using auto tuning self tuning Integral time I 1 to 1 999 s automatic adjustment using auto tuning self tuning Derivative time D 1 to 1 999 s automatic adjustment using auto tuning self tuning Alarm output range Absolute value alarm Same as the control range Other 0 to 100 FS Alarm hysteresis 0...

Страница 6: ...ause measurement errors 2 Models with 100 to 240 VAC and 24 VAC VDC are separate Models using 24 VDC have no polarity Panel Cutout Dimensions 44 8 44 8 84 78 6 48 48 60 min L 48 N 2 5 1 0 Mounting side by side group mounting of N Controllers 45 0 6 0 45 0 6 0 45 0 6 0 L Tightening screws 48 76 5 7 5 Adapter for flush mounting Panel Y92F 30 Adapter for flush mounting 58 E5CSV Note 1 The recommended...

Страница 7: ...d The ALM indicator lights when the alarm value 1 is being displayed PV SP Alarm Value Input Shift Display Alarm indicators ALM1 Alarm 1 Lights when the alarm 1 output is ON ALM2 Alarm 2 For future use Up Key Pressing the Up Key increases the SP alarm value display Keeping the Up Key pressed continues to increase the display value When the internal protect switch is ON press the Up Key while holdi...

Страница 8: ...100 0 100 1 700 1 300 1 300 850 850 400 400 199 9 199 9 199 9 0 0 0 0 0 0 0 99 99 99 99 99 99 Setting number 0 1 2 3 4 5 6 7 8 9 Input Pt100 JPt100 SP range 1 000 900 800 700 600 500 400 300 200 100 0 100 850 500 400 400 199 9 200 199 9 200 99 99 0 0 0 0 0 0 0 0 99 99 99 99 Setting number 0 1 2 3 4 5 6 7 8 9 Mode Key Display Order If the SP falls outside the temperature range when the temperature ...

Страница 9: ... ON OFF PID PID control ON ON OFF control OFF Control period 2 s ON 20 s OFF Direct reverse opera tion Direct operation cooling ON Reverse operation heating OFF Input shift display Enabled ON Disabled OFF Tempera ture Sensor selection Platinum resistance thermometer input ON Thermocouple input OFF Temper ature unit F ON C OFF 6 5 4 3 2 1 ON 6 5 4 3 2 1 ON Set value Alarm type Alarm output operatio...

Страница 10: ...or Switch 2 OFF control period 20 s Quick Control Response Using an SSR Switch 2 ON control period 2 s 2 Set direct reverse operation for the output Performing Heating Control for Heaters Switch 3 OFF Performing Cooling Control for Freezers Switch 3 ON 6 5 4 3 2 1 ON Switch 1 OFF ON OFF control OFF ON Control output SP 6 5 4 3 2 1 ON OFF ON Control output SP 6 5 4 3 2 1 ON Switch 1 ON PID control ...

Страница 11: ...input shift set the input shift value to h0 The shift range depends on the setting unit 5 Protect Switch When the protect switch is ON Up Key and Down Key operations are prohibited to prevent setting mistakes 6 5 4 3 2 1 ON Multi input Thermocouple Platinum Resistance Thermometer Control mode switch 5 OFF Multi input Thermocouple Platinum Resistance Thermometer Control mode switch 5 ON Set ting F ...

Страница 12: ...ystems Programmable logic controllers Human machine interfaces Remote I O Motion Drives Motion controllers Servo systems Inverters Control Components Temperature controllers Power supplies Timers Counters Programmable relays Digital panel indicators Electromechanical relays Monitoring products Solid state relays Limit switches Pushbutton switches Low voltage switch gear Sensing Safety Photoelectri...

Отзывы: