Temperature Controllers
E5CSV
5
1. Sensor Type Specification
Multi-input (Thermocouple/Platinum
Resistance Thermometer) Models
• Using Thermocouple Sensors, Control Mode Switch 5: OFF
•
The control range is -20
°
C to +20
°
C of the input temperature
range.
Note: 1.
The input indication range is the range that can be displayed for
the control range (-99 to 1999). If the input is within the control
range but exceeds the display range (-99 to 1999), values below
-99 will be displayed as “
[[[
“ and values above 1,999 will be
displayed as “
]]]
.”
2.
If unit is changed to 1 degree when the SP and alarm value for
the temperature range are displayed in 0.1-units from 0.0 to
199.9 or 0.0 to 99.9, the values will be multiplied by 10 (e.g., 0.5
becomes 5). If the unit is changed in the reverse direction, the
values will be divided by 10. After changing the range, set the
SP and alarm value again.
• Using Platinum Resistance Thermometers,
Control Mode Switch 5: ON
•
The control range is -20
°
C to +20
°
C of the input temperature
range.
Note: 1.
The input indication range is the range that can be displayed for
the control range (-99 to 1999). If the input is within the control
range but exceeds the display range (-99 to 1999), values below
-99 will be displayed as “
[[[
“ and values above 1,999 will be
displayed as “
]]]
.”
2.
If unit is changed to 1 degree when the SP and alarm value for
the temperature range are displayed in 0.1-units from 0.0 to
199.9 or 0.0 to 99.9, the values will be multiplied by 10 (e.g., 0.5
becomes 5). If the unit is changed in the reverse direction, the
values will be divided by 10. After changing the range, set the
SP and alarm value again.
ST (Self-tuning) Features
Executing AT (Auto-tuning)
■
Electrical Life Expectancy
Curve for Relays (Reference
Values)
Input
K
J
L
T
U
N
R
SP
range
1,700
1,600
1,500
1,400
1,300
1,200
1,100
1,000
900
800
700
600
500
400
300
200
100
0
-100
1,700
1,300
1,300
850
850
400
400
199.9
199.9
199.9
0.0
0.0
0.0
0
-99
-99
-99
-99
-99
-99
Setting number
0
1
2
3
4
5
6
7
8
9
Input
Pt100
JPt100
SP
range
1,000
900
800
700
600
500
400
300
200
100
0
-100
850
500
400
400
199.9
200
199.9
200
99
99
0.0
0
0
0.0
0
0
-99
-99
-99
-99
Setting number
0
1
2
3
4
5
6
7
8
9
Mode Key Display Order
•
If the SP falls outside the temperature
range when the temperature range is
changed, the SP will be displayed first.
The SP will be changed automatically
either to the minimum value or the
maximum value, whichever is nearest.
•
If the alarm value falls outside the
temperature range when the
temperature range is changed, the
alarm value will be displayed first. The
alarm value will be changed
automatically to the maximum value in
the new temperature range.
PV
SP
Alarm value 1
Input shift value
Power ON
Press the Key.
Press the Key.
Press the Key.
Press the Key.
ST (self-tuning) is a function that finds PID constants by using step
response tuning (SRT) when Controller operation begins or when
the set point is changed. Once the PID constants have been
calculated, ST is not executed when the next control operation is
started as long as the set point remains unchanged. When the ST
function is in operation, be sure to turn ON the power supply of the
load connected to the control output simultaneously with or before
starting Controller operation.
AT (auto-tuning) is executed by pressing the
U
Up and
D
Down
Keys for at least 2 s while the PV is displayed. The deviation
indicators flash during auto-tuning (AT) execution. AT will be
cancelled by performing the same operation that AT is executing
during AT operation. Flashing stops when AT is completed.
Note:
One of the deviation indicators (
▲■▼
) will flash.
AT execution in progress
Press for
at least 2 s.
Press for
at least 2 s.
U D
U D
AT execution in progress
AT execution
AT cancelled
500
300
100
50
30
10
5
3
1
0
1
2
3
4
5
6
Switching current (A)
Life (
×
10
4
operations)
E5CSV
250 VAC, 30 VDC
(resistive load)
cos
φ
= 1
6
Temperature Controllers
E5CSV
2. Operation Settings
Use the control mode switches (
) to change the
control mode. (All switches are OFF for the default settings.)
Note:
The previous name Pt100 has been changed to JPt100 in
accordance with revisions to JIS. The previous name J-DIN has
been changed to L in accordance with revisions to DIN
standards.
3. Alarm Modes
Select the number of the alarm mode switch
when changing
the alarm mode. (The default is 2).
Note: 1.
No alarm. The alarm value (alarm operation display) will not
be displayed when the setting is 0 or 9 even if the selection
key is pressed.
Alarm Setting Range
X: 0 to FS (full scale); Y: Within temperature range
The value of X is the deviation setting for the SP (set point).
2.
Standby Sequence Function (The standby sequence
operates when the power is turned ON.)
For details on the position of the temperature range switch, control mode switches, and alarm mode switch, refer to page 4.
Function selection
1
2
3
4
5
6
ON/OFF
PID
PID control
ON
ON/OFF control
OFF
Control
period
2 s
ON
20 s
OFF
Direct/
reverse
opera-
tion
Direct operation
(cooling)
ON
Reverse operation
(heating)
OFF
Input
shift
display
Enabled
ON
Disabled
OFF
Tempera-
ture
Sensor
selection
Platinum
resistance thermometer
input
ON
Thermocouple
input
OFF
Temper-
ature
unit
°
F
ON
°
C
OFF
6
5
4
3
2
1
ON
6
5
4
3
2
1
ON
Set
value
Alarm type
Alarm output operation
0, 9
Alarm function OFF
OFF
1
Upper- and lower-
limit
2
Upper-limit
3
Lower-limit
4
Upper- and lower-
limit range
5
Upper- and lower-
limit with standby
sequence (See note
2.)
6
Upper-limit with
standby sequence
(See note 2.)
7
Lower-limit with
standby sequence
(See note 2.)
8
Absolute-value
upper-limit
0 1
2
3
45
6
7
8
9
X
SP
X
ON
OFF
SP
X
ON
OFF
X
SP
ON
OFF
X
SP
X
ON
OFF
X
SP
X
ON
OFF
X
SP
ON
OFF
X
SP
ON
OFF
0
Y
ON
OFF
Upper-limit
alarm
SP
Lower-limit
alarm
Alarm
output
ON
OFF
Upper-limit
alarm
SP
Lower-limit
alarm
Alarm
output
ON
OFF
Rising Temperature
Dropping Temperature
Note:
Turn OFF the power before changing the DIP switch settings on the E5CSV. Each of the switch settings will be enabled after the power is
turned ON.
9
Temperature Controllers E5CSV