CHAPTER 5 PARAMETERS
E5AK
5--18
·
The parameters in this mode can be used only when the “security” parameter (pro-
tect mode) is set to “0” to “2”.
·
This mode contains the auxiliary parameters for adjusting control. These parame-
ters include parameters for limiting the manipulated variable and set point, parame-
ters for switching between remote and local operation, and parameters for setting the
LBA (Loop Break Alarm), alarm hysteresis, and input digital filter values.
·
To select this mode when in the levels 0 and 1, setup, expansion, option and calibra-
tion modes, press the
key for 1 second minimum. The display changes to the
menu display. If you select [
] using the
key then press the
key for
1 second minimum, the controller enters the level 2 mode.
·
To select parameters in this mode, press the
key. To change parameter settings,
use the
or
keys.
·
The following table shows the parameters supported in this mode and the page where
the parameter is described.
Symbol
Parameter Name
Page
Remote/Local
5-19
SP mode
5-19
SP ramp time unit
5-20
SP ramp set value
5-20
LBA detection time
5-21
MV at stop
5-21
MV at PV error
5-21
MV upper limit
5-22
MV lower limit
5-22
MV change rate limit
5-22
Input digital filter
5-23
Open/close hysteresis
5-23
Alarm 1 hysteresis
5-24
Alarm 2 hysteresis
5-24
Alarm 3 hysteresis
5-24
Input shift upper limit (temperature)
5-24
Input shift lower limit (temperature)
5-24
Level 2 Mode