Using the E53-AKB, run/stop can be selected by event input. For details on how to
use event input, see 4.3 How to Use Event Input, page 4---8.
Using Event Input
3.6 Starting and Stopping Operation
E5AK
3--13
3.6 Starting and Stopping Operation
·
You can start and stop operation by changing the setting of the “run/
stop” parameter (level 0 mode).
·
You can switch the RUN/STOP function up to 100,000 times.
·
To stop operation, set the “run/stop” parameter to [
] (stop). In a
stop state, the “STOP” LED lights.
·
Operation cannot be stopped during auto-tuning.
·
On a standard type controller, specify the manipulated variable (---5.0 to
105.0%) in the “MV at stop” parameter (level 2 mode) to output the
manipulated variable during stop.
Factory-set to “0.0:0.0%”.
·
On a position-proportional type controller, you can select either of the
open, close or hold status. In an open status, only control output 1 is ON.
In a close status, only control output 2 is ON. In a hold status, both con-
trol outputs 1 and 2 are OFF. Factory-set to “hold.”
The following example describes the procedure to follow to stop control
during operation of the controller.
(1) Select the menu display, and select [
] (level 0 mode) using the
or
keys. For details on selecting the menu display, see page
1-8.
(2) Press the
key to enter the level 0 mode. The PV and SP are dis-
played.
(3) Press the
key until [
] (“run/stop” parameter) is displayed.
(4) Press the
key to select [
] (stop). The “STOP” LED lights,
and operation stops.
To resume operation, follow the above procedure to select [
] (“run”).
The “STOP” LED goes out and operation starts.
F
Manipulated vari-
able at stop
Setting Example
1 second min.