E5AK
5--15
Manual reset value
Conditions of Use
The control must be either standard con-
trol or advanced PID control, ST must be
set to OFF, and the “integral time” parame-
ter must be set to “0”.
·
Sets the required manipulated variable to remove offset during stabilization of P or
PD control.
Setting Range
Unit
Default
0.0 to 100.0
%
50.0
E5AK-AA2 AC100-240
E5AK-AA2 AC/DC24
Hysteresis (heat)
Hysteresis (cool)
Conditions of Use
The control system must be ON/OFF con-
trol.
·
Sets the hysteresis for ensuring stable operation at ON/OFF switching.
·
In standard control, use the “hysteresis (heat)” parameter. The “hysteresis (cool)”
parameter cannot be used.
·
In heating and cooling control, the hysteresis can be set independently for heating
and cooling. Use the “hysteresis (heat)” parameter to set the heating side hysteresis,
and use the “hysteresis (cool)” parameter to set the cooling side hysteresis.
Parameter
Setting Range
Unit
Default
Hysteresis (heat)
0.01 to 99.99
%FS
0.10
Hysteresis (cool)
0.01 to 99.99
%FS
0.10
F
Related article
4.1 Selecting the Control Method
/
ON/OFF control (page 4-4)
F
Related parameters
“Control output 1 assignment” “Control output 2 assignment” (setup mode)
“PID / ON/OFF” (expansion mode)
E5AK-AA2 AC100-240
E5AK-AA2 AC/DC24
Level 1 Mode
Function
Comment
Model
Function
Comment
See
Model