2.3 Wiring Terminals
E5AK
2--11
·
Connect event inputs 1 and 2 (EV1/2) to terminal Nos.18 to 20, and event
events 3 and 4 (EV3/4) to terminal Nos.24 to 26. However, note that ter-
minal Nos.18 to 20 cannot be used on controllers having a communica-
tions function.
·
Connect the event inputs as follows:
20
19
18
26
25
24
+
+
--
Event input 1 and 2
Event input 3 and 4
EV1
EV2
COM
EV3
EV4
COM
+
+
--
Terminals 18 and 24 (COM) are connected internally.
·
Use event inputs under the following conditions:
Contact input
ON: 1 k
W
max., OFF: 100 k
W
min.
No-contact input ON: residual voltage 1.5 V max.,
OFF: leakage current 0.1 mA max.
·
Polarities during no-contact input are as follows:
20
19
18
26
25
24
+
+
--
Event input 1 and 2
Event input 3 and 4
EV1
EV2
COM
EV3
EV4
COM
+
+
--
·
Connect transfer output (TRSF) to terminal Nos. 29 and 30.
·
The internal equalizing circuit for transfer output is as follows:
30
29
4 to 20mA
L
+
--
·
Transfer output specifications are as follows:4 to 20 mA,
Permissible load impedance: 600
W
max.,
Resolution: Approx. 2600
·
Terminal Nos.18 to 20, 31 and 32 can be used only on controllers having
a communications units (E53-AK01/02/03).
·
For details on wiring, see Chapter 6, Using the Communications Func-
tion.
F
Event input
10
9
8
7
6
5
4
3
2
1
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
31 32
33
F
Transfer output
F
Communications