E5AK
5--9
Valve opening monitor
Conditions of Use
Control must be position-proportional con-
trol
·
Monitors the valve opening during position-proportional control.
Moniter Range
Unit
-10 to +110
EU
F
Related article
4.1 Selecting the Control Methed/Position-proportional control (page 4-3)
E5AK-PRR2 AC100-240
E5AK-PRR2 AC/DC24
Run/Stop
·
This parameter is used for checking the operating status of the controller, and for
specifying start and stop of operation.
·
When the “run/stop” function is assigned to event input, “stop” is set when event in-
put is ON, and “run” is set when event input is OFF. There is no order of priority in
key operations.
·
To start operation, set this parameter to [
] press the
or
keys. To stop
operation, set this parameter to [
]. When operation is stopped, the “STOP”
LED lights.
·
Default is [
]
F
Related article
3.6 Starting and Stopping Operation (page 3-13)
Level 0 Mode
Function
Monitor
See
Model
Function
Example
of use
See