CHAPTER 4 APPLIED OPERATION
E5AK
4--8
4.3 How to Use Event Input
·
When using event input, mount the option unit (E53-AKB). Up to two
E53-AKB units can be mounted on the E5AK, and two event inputs can
be used for each E53-AKB unit.
E53-AKB
×
1 unit
: 2 event inputs
E53-AKB
×
2 units : 4 event inputs
·
Event inputs can be switched up to 100,000 times.
·
You can choose from the following five event input functions:
Multi-SP
Run/Stop
Remote/Local
Auto/Manual
SP mode
·
In the case of the multi-SP function, the number of event inputs (event
input 1 or 2) set in the “multi-SP function” parameter (option mode) are
used. When four event inputs are used, the multi-SP function is auto-
matically assigned to event inputs 1 and 2 for the designated number.
When two event inputs are used, the multi-SP function is automatically
assigned to event inputs 3 and 4 for the designated number.
·
Other functions are assigned to event inputs 1 to 4 not used for the mul-
ti-SP function according to the setting of the “event input assignment 1 to
4” parameters (option mode). However, note that “event input assignment
1/2” parameters cannot be used when only one unit of the E53-AKB is
installed.
4 event inputs
2 event inputs
Event input
Multi-SP
Other event input functions
3
4
3
4
1
2
0
1
2
M
ul
ti-
SP
funct
ion
·
The following table shows the relationship between the settings and
functions of the “event input assignment 1 to 4” parameters.
Setting
Function
Event input disabled
ON : Stop
/OFF : Run
ON : Remote
/OFF : Local
ON : Manual
/OFF : Auto
ON : RSP
/OFF : LSP
J
Event input
assignments