Simplicity on the Worksite
Solutions Guide for FAQs: E5
@
N
Setting Heater Burnout Alarms
5-1
Setting He
ater Burno
ut Alarm
s
Setting Heater Burnout Alarms
The procedure to output heater burnout alarms is given step by step in this section.
A heater burnout alarm operates by detecting the heater current with a current transformer (CT). If
the detected current is less than the specified heater burnout detection current even though the
control output is ON, a heater burnout will be assumed and an alarm will be output.
CT
SSR
Heater burnout alarm:
E5
@
N
Turns ON if the heater current is below the
set value of the heater burnout detection
current.
You can use only alarm 1 for the heater burnout alarm.
To output only the heater burnout alarm from auxiliary output 1, set the alarm type for alarm 1 to 0 (no
alarm).
If the alarm type is set to any other value, alarm 1 will turn ON both for the heater burnout alarm and a
temperature alarm.
You set this parameter in the Initial Setting Level. The parameter is set to 2 (Upper-limit Alarm) by default.
Confirm that the HB ON/OFF parameter in the Advanced Function Setting Level is set to ON (enabled).
The default setting is ON.
1
Set the Alarm 1 Type parameter to 0.
alt1
(ALT1): Indicates
←
the Alarm 1 parameter.
←
Default setting is 2
(Upper-limit Alarm).
Initial Setting Level
Change the set value to
0 with the (Up
and Down) Keys.
Initial Setting Level
2
Confirm that the heater burnout alarm is enabled.
hbu
(HBU): Indicates the
←
HB ON/OFF parameter.
←
Default setting is
on
(ON):
Enabled.
Advanced Function
Setting Level
If
off
(OFF) is displayed, press the (Up)
Key to change to
on
(ON) to enable the heater
burnout alarm.