Simplicity on the Worksite
Solutions Guide for FAQs: E5
@
N
Using ON/OFF Control
2-2
Using ON/OF
F
Control
You set this parameter in the Initial Setting Level. The parameter is set to ON/OFF control by default.
You set this parameter in the Initial Setting Level. The parameter is set to reverse operation by
default.
Step 2 Setting ON/OFF Control Parameters
1
Setting ON/OFF Control
Press the
(Level) Key for
at least 3
seconds.
Press the (Mode) Key
several times to display
cntl
(CNTL).
Operating Display
←
cntl
(CNTL): Indicates the Control Method
parameter.
←
Default setting is
onof
(ONOF): ON/OFF
control.
Initial Setting Level
←
in-t
(IN-T) will be displayed to
show that the Initial Setting Level
has been entered.
Press the Key for at least 3 seconds.
Initial Setting Level
←
Flashes 3 times.
2
Change the parameter with the Key.
3
If
pid
(PID control) is displayed, press
the (Down) Key to change to
onof
(ONOF) (ON/OFF control).
Turn ON the power supply.
1
(When finished, press the (Level) Key for at least 1 second to return
to the operation display.)
2
Setting Direct or Reverse Operation
Press the (Mode) Key
several times to display
orev
(OREV).
←
orev
(OREV): Indicates the
Direct/Reverse Operation parameter.
←
Default setting is
or-r
(OR-R):
Direct operation.
Initial Setting Level
Change the parameter with the Key.
1
Change the set value with the
(Up and Down) Keys.
or-r
(OR-R): Reverse operation (default)
or-d
(OR-D): Direct operation