![Omron CVM1D Скачать руководство пользователя страница 365](http://html1.mh-extra.com/html/omron/cvm1d/cvm1d_operation-manual_742532365.webp)
360
The following diagram demonstrates the flow of processing and the switches
that are used for execution control.
Process A
Process B
Process C
Loading
Part Installation
Inspection/discharge
SW1
SW2
SW3
SW4
The program for this process, shown below, utilizes the most basic type of step
programming: each step is completed by a unique SNXT(009) that starts the
next step. Each step starts when the switch that indicates the previous step has
been completed turns ON.
(009)
SNXT 012800
(008)
STEP 012800
(009)
SNXT 012801
(008)
STEP 012801
(009)
SNXT 012802
(008)
STEP 012802
(009)
SNXT 012803
(008)
STEP 012803
0000
01
0000
02
0000
03
0000
04
Programming for process A
Programming for process B
Programming for process C
Process
A started.
Process
A reset.
Process
B started.
Process
B reset.
Process
C started.
Process
C reset.
00000
LD
000001
00001
SNXT(009)
012800
00002
STEP(008)
012800
Process A
00100
LD
000002
00101
SNXT(009)
012801
00102
STEP(008)
012801
Process B
00100
LD
000003
00101
SNXT(009)
012802
00102
STEP(008)
012802
Process C
00200
LD
000004
00201
SNXT(009)
012803
00202
STEP(008)
012803
Address Instruction
Operands
SW1
SW2
SW3
SW4
STEP DEFINE and STEP START: STEP(008)/SNXT(009)
Section 5-29
Содержание CVM1D
Страница 462: ...SYSMAC CVM1D Duplex System Programmable Controllers Operation Manual Revised August 2001...
Страница 463: ...iv...