![Omron CVM1D Скачать руководство пользователя страница 344](http://html1.mh-extra.com/html/omron/cvm1d/cvm1d_operation-manual_742532344.webp)
339
Example
When CIO 000000 is OFF in the following example, the following instruction
would convert the seconds given in D00000 and D00001 to hours, minutes, and
seconds and store the results in D00100 and D00101 as shown.
(144)
HMS
D00000
D00100
D00000
5
9
2
7
D00001
1
0
1
3
D00100
3
2
0
7
D00101
2
8
1
5
10,135,927 s
2,815 hrs, 32 min, 07 s
00000
LD NOT
000000
00001
HMS(144)
D00000
D00100
0000
00
Address Instruction
Operands
5-26-3 CALENDAR ADD: CADD(145)
Variations
j
CADD(145)
(145)
CADD
C
T
R
T: 1
st
time word
CIO, G, A, T, C, #, DM
R: 1
st
result word
CIO, G, A, DM
C: 1
st
calendar word CIO, G, A, T, C, DM
Operand Data Areas
Ladder Symbol
Description
When the execution condition is OFF, CADD(145) is not executed. When the ex-
ecution condition is ON, CADD(145) adds the time in words T and T+1 to the
calendar data in words C, C+1, and C+2, and outputs the result to words R, R+1,
and R+2.
CADD(145) (and the Calendar/Clock Area (G001 to G004)) corrects for leap
year.
The following table shows the format of calendar information. The format is the
same for the results output to R, R+1, and R+2.
Word
Bits
Contents
Possible values
C
00 to 07
Seconds
00 to 59
08 to 15
Minutes
00 to 59
C+1
00 to 07
Hours
00 to 23 (24-hour system)
08 to 15
Day of month
01 to 31 (adjusted by month and for leap year)
C+2
00 to 07
Month
01 to 12
08 to 15
Year
00 to 99 (Rightmost two digits of year)
The following table shows the format of the time information.
Word
Bits
Contents
Possible values
T
00 to 07
Seconds
00 to 59
08 to 15
Minutes
00 to 59
T+1
00 to 07
Hours
0000 to 9999
Precautions
C, C+1, C+2, T, and T+1 must be BCD and in the proper format.
Note Refer to page 101 for general precautions on operand data areas.
Flags
ER (A50003):
Time or calendar data is not in the correct format
(including impossible dates such as Feb. 30).
Content of
*
DM word is not BCD when set for BCD.
EQ (A50006):
ON when the content of R, R+1, and R+2 is 0 after execu-
tion.
Time Instructions