50
Replacement Checklists
Section 3-6
3-6-1
Pattern A: Mixed Mid-sized and Large PLCs
The pattern A system contains mid-sized (C200H
@
or CS-series) PLCs and
large (C500, C1000H, or C2000H) PLCs. Set the replacement PC Link Units
as shown in the following table.
Checklist 1
Use the following checklist when replacing a C500-LK009-V1 with a CVM1-
LK401.
Item
Original Unit: C500-LK009-V1
Replacement Unit: CVM1-LK401
Remarks
CPU Bus
Unit unit
number
Not applicable
Any unique number in setting
range (Do not set the same unit
number on two CPU Bus Units in a
PLC.)
Do not mount more PC
Link Units than allowed.
Node
address
Check setting on pins 1 to 5: [ ]
Set the CVM1-LK401’s node
address to the same node address
that was set on the C500-LK009-
V1. (Set the rotary switches in 2-
digit decimal.)
Check the node address
settings on other nodes in
the PC Link to confirm
that the same address is
not already taken.
A Unit error will
not
occur
if the same node address
is set on two PC Link
Units in the same PC
Link, but there will be
data errors in the LR
Area.
Pins
1 to 5
Node
address
Pins
1 to 5
Node
address
00000
0
10000
16
00001
1
10001
17
00010
2
10010
18
00011
3
10011
19
00100
4
10100
20
00101
5
10101
21
00110
6
10110
22
00111
7
10111
23
01000
8
11000
24
01001
9
11001
25
01010
10
11010
26
01011
11
11011
27
01100
12
11100
28
01101
13
11101
29
01110
14
11110
30
01111
15
11111
31
Number of
LR Bits
Check setting on pins 6 to 8 of SW1:
[
] Bits / [
] Units
Set the same number of LR bits
that was set on the C500-LK009-
V1.
Make the “number of LR
bits” setting on the polling
node (node 0) in the PC
Link. The “number of LR
bits” settings on the other
nodes (polled nodes) are
ignored.
Set the same level/link
number (next item in
table) that was set on the
Unit being replaced. If an
invalid setting is set, the
max. valid number of bits
setting will be used
instead.
The number of Units
listed in parentheses for
the C500-LK009-V1 is the
maximum number of
Units for the C500 PLC.
The (*1) setting is invalid
for the C500.
Pins
6 to 8
Pin 3 of SW3
Pins
6 to 8
Pin 3
1 (Single-
level LK009)
0 (Multi-level)
1 (Single-
level LK009)
0 (Multi-
level)
000
32 bits/
32 (8) Units
32 bits/
16 (8) Units
000
32 bits/
32 Units
32 bits/
16 Units
001
64 bits/
16 (8) Units
64 bits/
8 (4) Units
001
64 bits/
16 Units
64 bits/
8 Units
010
128 bits/
8 (4) Units
128 bits/
4 (2) Units
010
128 bits/
8 Units
128 bits/
4 Units
011
256 bits/
4 (2) Units
256 bits/
2 (*1) Units
011
256 bits/
4 Units
256 bits/
2 Units
100
512 bits/
2 (*1) Units
Invalid setting
100
512 bits/
2 Units
Invalid set-
ting
101
Invalid set-
ting
101
Invalid set-
ting
110
110
111
111
NODE
No.
×
10
1
×
10
0
0
0
Содержание CVM1 Series
Страница 1: ...Cat No W434 E1 01 SYSMAC CVM1 CV Series CVM1 LK401 PC Link Unit This manual is PDF file only...
Страница 2: ...CVM1 LK401 PC Link Unit Operation Manual Produced July 2004...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 41: ...26 Differences from Earlier PC Link Units Section 2 6...
Страница 77: ...62 Replacement Checklists Section 3 6...
Страница 95: ...80 Link Adapter Specifications Appendix B...
Страница 101: ...86 PC Link System I O Response Time Appendix C...
Страница 103: ...88 PC Link Settings and Status Areas Appendix D...